{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046980-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046980-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046980-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046980-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 series, 3ABD00046980-D, wall-mounted LV AC drive, 11 kW / 25 A normal duty, 7.5 kW / 17 A heavy duty, IP21, NEMA 1, Frame R2, IE2.","salesMarkdown":"The heavy-duty rating (7.5 kW, 17 A) applies when you need sustained overload capability — think crushers, mixers, or hoists that draw more current during start or jam conditions. If your motor nameplate sits between these curves, size to the heavy-duty column to avoid nuisance trips. ## Installation notes Wall-mount only — no DIN-rail option. IP21 means no washdown tolerance; keep it in a cabinet or dry machine bay. NEMA 1 knockouts accept standard conduit. Frame R2 determines gland-plate layout and minimum side clearance per the manual. Input voltage range 380–415 V three-phase covers most European and Asian industrial supplies; the 47.5–63 Hz frequency tolerance handles weak grids or generator feeds.","metaTitle":"ABB 3ABD00046980-D ACS880-01 Drive, 11 kW, IP21, Frame R2","metaDescription":"ABB ACS880-01 3ABD00046980-D wall-mounted drive, 11 kW normal duty (25 A), 7.5 kW heavy duty (17 A). IP21, NEMA 1, IE2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"11 kW","Output Current, Normal Use (In)":"25 A","Output Power, Heavy-Duty Use (PhD)":"7.5 kW","Output Current, Heavy-Duty Use (IhD)":"17 A","Output Power, Light-Overload Use (PlD)":"11 kW","Output Current, Light-Overload Use (IlD)":"24 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046980-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046980-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R2. This determines physical mounting dimensions and cable entry layout."},{"question":"What are the normal-duty and heavy-duty ratings?","answer":"Normal duty: 11 kW output at 25 A. Heavy duty: 7.5 kW output at 17 A. Light-overload rating matches the normal-duty figure at 11 kW / 24 A."},{"question":"What input voltage and frequency does it accept?","answer":"380–415 V three-phase, 47.5–63 Hz."},{"question":"What enclosure protection does it have?","answer":"IP21 with NEMA Type 1 enclosure — suitable for indoor, dry locations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046980-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046980-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}