{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00047429-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00047429-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00047429-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00047429-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-033A-4+X1583+N7551, LV AC wall-mounted drive, 15 kW normal use, 32 A output, Frame R3, IP21, NEMA Type 1, IE2.","salesMarkdown":"The 3ABD00047429-D: The drive lists three duty points: normal use at 15 kW / 32 A, heavy-duty at 11 kW / 24.6 A, and light-overload at 15 kW / 30.4 A. The normal-use rating applies to variable-torque loads such as centrifugal fans and pumps, where the current demand drops with speed. Frame size R3 is the physical package that houses this power stage; it determines the mounting footprint and the available conduit entries. ## Mounting and enclosure fit Wall-mounted, IP21, NEMA Type 1. That means it's intended for indoor, non-condensing environments — think equipment rooms, mechanical mezzanines, or enclosed machine cabinets. The NEMA 1 rating allows finger-safe access to the interior but doesn't seal against dust or moisture. If the installation is in a washdown area or outdoors, you'd need a higher IP rating or a separate enclosure.","metaTitle":"ABB 3ABD00047429-D ACH580 Drive, 15 kW, 32 A, Frame R3","metaDescription":"ABB ACH580-01 wall-mounted drive, 15 kW normal use, 32 A output, IP21, NEMA 1, IE2. Active production. Frame R3. 380-480 V 3-phase input.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R3","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"32 A","Output Power, Heavy-Duty Use (PhD)":"11.0 kW","Output Current, Heavy-Duty Use (IhD)":"24.6 A","Output Power, Light-Overload Use (PlD)":"15.0 kW","Output Current, Light-Overload Use (IlD)":"30.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00047429-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00047429-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00047429-D?","answer":"The frame size is R3."},{"question":"What are the key output ratings for this drive?","answer":"Normal use: 15 kW at 32 A. Heavy-duty use: 11 kW at 24.6 A. Light-overload use: 15 kW at 30.4 A."},{"question":"What input voltage and frequency does it accept?","answer":"It accepts 380-480 V three-phase input at 47.5 to 63 Hz."},{"question":"What is the enclosure protection rating?","answer":"IP21 with NEMA Type 1 enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00047429-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00047429-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}