{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00047994-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00047994-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00047994-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00047994-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 LV AC general purpose wall-mounted drive, 55 kW / 106 A normal use, 45 kW / 87 A heavy duty, IP21, IE2, Frame R5, 380-480 V 3-phase.","salesMarkdown":"The ABB 3ABD00047994-D is an LV AC general purpose wall-mounted drive rated 55 kW normal use at 106 A, with a heavy-duty rating of 45 kW at 87 A. It runs on 380-480 V 3-phase input, covers 47.5 to 63 Hz, and carries an IE2 efficiency level. ## Sizing by duty class Normal-use 55 kW / 106 A covers variable-torque loads like fans and pumps. Heavy-duty 45 kW / 87 A handles constant-torque applications such as conveyors or extruders where overload margins are tighter. The light-overload rating matches the normal-use power but at 100 A — a slight current derating that can matter when cable sizing is marginal.","metaTitle":"ABB 3ABD00047994-D ACS580-01 Drive, 55 kW, 106 A, IP21, R5","metaDescription":"ABB ACS580-01 wall-mounted drive, 55 kW normal use (106 A), 45 kW heavy duty (87 A). IP21, IE2, active production. Frame R5. 380-480 V, 3-phase. Order to spec.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R5","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"55 kW","Output Current, Normal Use (In)":"106 A","Output Power, Heavy-Duty Use (PhD)":"45 kW","Output Current, Heavy-Duty Use (IhD)":"87 A","Output Power, Light-Overload Use (PlD)":"55 kW","Output Current, Light-Overload Use (IlD)":"100 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00047994-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00047994-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for this drive?","answer":"Normal use: 55 kW at 106 A. Heavy duty: 45 kW at 87 A. Light overload: 55 kW at 100 A."},{"question":"What is the frame size and enclosure rating?","answer":"Frame size R5, IP21 enclosure, NEMA Type 1, wall-mounted."},{"question":"What input voltage and frequency does it accept?","answer":"380-480 V 3-phase, 47.5 to 63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00047994-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00047994-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}