{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048129","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048129","canonicalUrl":"https://aoctrl.com/abb/3ABD00048129","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048129","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380 series, LV AC machinery drive module, 3ABD00048129, 4 kW normal-use output, 9.4 A, 380-480 V 3-phase input, Frame R1, IP20, IE2.","salesMarkdown":"The ABB 3ABD00048129 is an LV AC machinery drive module, rated for 4 kW normal-use output at 9.4 A on a 380-480 V three-phase supply. Frame size R1, IP20 open-type enclosure, IE2 efficiency class. Active in production. The drive carries three duty curves. Normal use (Pn) delivers 4 kW at 9.4 A — the spec to match against a constant-torque load like a conveyor or pump. Heavy-duty use (PhD) drops to 3 kW at 7.2 A, sized for a higher peak torque demand such as a crusher or extruder. Light-overload use (PlD) stays at 4 kW but at 8.9 A, a slightly lower current than normal use; it suits variable-torque applications like fans where full current is rarely sustained.","metaTitle":"ABB 3ABD00048129 ACS380 Drive, 4 kW, 9.4 A, Frame R1","metaDescription":"Active ABB ACS380-040C-09A4-4+K492+L515+L535 drive. 4 kW normal use, 9.4 A output, 380-480 V 3-phase input. Frame R1, IP20, IE2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"8.9 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048129","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048129/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00048129?","answer":"Frame size R1."},{"question":"What are the key output ratings?","answer":"Normal use: 4 kW, 9.4 A. Heavy-duty use: 3 kW, 7.2 A. Light-overload use: 4 kW, 8.9 A."},{"question":"What input voltage and frequency does it accept?","answer":"380-480 V three-phase, 47.5-63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048129","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048129 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}