{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048197-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048197-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048197-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048197-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01, 3ABD00048197-D, wall-mounted LV AC drive, 380–415 V 3-phase, 75 kW / 145 A normal use, IP21, frame R6.","salesMarkdown":"The ABB 3ABD00048197-D is an ACS880-01 wall-mounted single drive rated 75 kW normal-use output at 145 A, with a heavy-duty rating of 55 kW at 105 A. It runs on 380–415 V three-phase input, 48–63 Hz, and carries IP21 protection in a NEMA Type 1 enclosure. Frame size is R6. Normal-use current of 145 A (75 kW) is the headline number for continuous motor duty. The heavy-duty curve drops to 105 A (55 kW) — that's the figure to size against if the load profile includes frequent starts or high breakaway torque. Light-overload use sits at 138 A (75 kW), close to the normal-use line but with a slightly different thermal model. For a 400 V class drive, the 145 A normal-use rating covers a standard 75 kW induction motor; the 105 A heavy-duty rating aligns with a 55 kW motor on a tougher duty cycle. Wall-mounted, IP21, NEMA Type 1. Suitable for indoor, non-condensing environments. Frame R6 determines the physical footprint and mounting hole pattern — verify panel clearance against the ACS880-01 R6 dimensional drawing before laying out the cabinet.","metaTitle":"ABB 3ABD00048197-D ACS880-01 Drive, 75 kW, 145 A, IP21, R6","metaDescription":"ABB ACS880-01 wall-mounted drive, 75 kW normal use, 145 A, IP21, frame R6. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R6","Frequency (f)":"48 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048197-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048197-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00048197-D?","answer":"Frame size R6."},{"question":"What input voltage and frequency does this drive accept?","answer":"380–415 V three-phase, 48–63 Hz."},{"question":"What are the normal-use and heavy-duty ratings?","answer":"Normal use: 75 kW, 145 A. Heavy-duty use: 55 kW, 105 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048197-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048197-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}