{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048299-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048299-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048299-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048299-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-363A-4+P973, LV AC general purpose wall-mounted drive, 200 kW, 363 A, IP21, NEMA 1, IE2.","salesMarkdown":"## Fit and installation The 3ABD00048299-D: Frame size R9 — that's the physical envelope you're working with. Wall-mounted, so no floor pad or cabinet kit required, but the IP21 / NEMA 1 enclosure means it's for indoor, dry locations. Plan for top and bottom gland plates; the drive is heavy enough that a lifting bracket or two-person carry is the field reality. ## Duty ratings at a glance Normal use (light overload) delivers 200 kW / 363 A. Heavy-duty use drops to 160 kW / 293 A — that's your constant-torque or high-starting-torque number for pumps, fans, compressors on a tough cycle. Light-overload use is listed at 200 kW / 345 A, a slightly different current curve for applications that never push the drive hard. Pick the column that matches your motor's load profile.","metaTitle":"ABB 3ABD00048299-D ACS580-01-363A-4+P973, 200 kW, 363 A","metaDescription":"ABB ACS580-01-363A-4+P973 wall-mounted drive, 200 kW normal use, 363 A, IP21, NEMA 1, IE2. Active production. Frame R9. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R9","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"200 kW","Output Current, Normal Use (In)":"363 A","Output Power, Heavy-Duty Use (PhD)":"160 kW","Output Current, Heavy-Duty Use (IhD)":"293 A","Output Power, Light-Overload Use (PlD)":"200 kW","Output Current, Light-Overload Use (IlD)":"345 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048299-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048299-D/alternatives.json"},"ai":{"faq":[{"question":"What is 3ABD00048299-D's frame size?","answer":"Frame size R9."},{"question":"What is the frequency range for this drive?","answer":"47.5 to 63 Hz."},{"question":"What are the normal-use and heavy-duty power ratings?","answer":"Normal use: 200 kW / 363 A. Heavy-duty use: 160 kW / 293 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048299-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048299-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}