{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048501-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048501-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048501-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048501-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-05A7-4+N7511+P944+K492, LV AC general-purpose wall-mounted drive, 2.2 kW, 5.6 A, 380-480 V, 3-phase, IP20, IE2, Frame R1.","salesMarkdown":"The ABB 3ABD00048501-D is a wall-mounted LV AC general-purpose drive from the ACS580-01 series, rated 2.2 kW normal-use output at 5.6 A on a 380–480 V three-phase supply. Heavy-duty duty cycle drops to 1.5 kW at 4.0 A, so if the motor is oversized or the load has intermittent peaks, that's the rating to size against. IE2 efficiency is the baseline for this power class; it won't win energy rebates but meets current EU regulation for fixed-speed pumps and fans. IP20 enclosure is open-type — fine inside a clean panel, not for washdown or dust. Frequency range 47.5–63 Hz handles 50 Hz and 60 Hz supplies, so the same unit works on either side of the pond.","metaTitle":"3ABD00048501-D ABB ACS580-01-05A7-4+N7511+P944+K492, 2.2 kW","metaDescription":"ABB ACS580-01-05A7-4+N7511+P944+K492 LV AC general-purpose wall-mounted drive. 2.2 kW normal use, 5.6 A, 380-480 V, 3-phase. IP20, IE2. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4.0 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Output Current, Light-Overload Use (IlD)":"5.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048501-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048501-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for normal and heavy-duty use?","answer":"Normal-use output is 2.2 kW at 5.6 A. Heavy-duty use is 1.5 kW at 4.0 A. Light-overload use is 2.2 kW at 5.3 A. The heavy-duty figure governs sizing for constant-torque loads like conveyors or positive-displacement pumps."},{"question":"What efficiency class and protection rating does it have?","answer":"IE2 efficiency class and IP20 degree of protection. Suitable for indoor panel installation; not rated for outdoor or wet environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048501-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048501-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}