{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048684-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048684-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048684-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048684-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 general purpose LV AC drive, 3ABD00048684-D, Frame R1, 4 kW / 9.4 A normal use, 380-480 V 3-phase, IP21, IE2.","salesMarkdown":"## Drive selection for the install window The 3ABD00048684-D is an ABB ACS580-01 general-purpose wall-mounted drive rated 4 kW normal-use power at 9.4 A output current on a 380-480 V three-phase supply. Frame R1 keeps the panel footprint compact for a 4 kW machine; the IP21 enclosure suits clean indoor environments without additional cabinet protection. Efficiency class IE2 meets the baseline for most industrial applications where premium IE3 is not contractually required. Three overload profiles are defined: normal use at 4 kW / 9.4 A, heavy-duty at 3.0 kW / 7.2 A, and light-overload at 4.0 kW / 8.9 A. The heavy-duty figure governs continuous operation on a constant-torque load like a conveyor or positive-displacement pump; the normal-use figure covers variable-torque loads (centrifugal fans, pumps) where the drive can run at the higher current without exceeding thermal limits. Light-overload matches the normal-use power but at a slightly lower current, which may apply when the motor is oversized relative to the load. Frame R1 dimensions should be verified against the panel layout to confirm gland-plate clearance and cable bend radius for the incoming 3-phase supply.","metaTitle":"ABB 3ABD00048684-D ACS580-01-09A5-4+X1574 Drive, 4 kW, 9.4 A","metaDescription":"ABB ACS580-01 general purpose drive, 3ABD00048684-D, 4 kW normal use, 9.4 A, 380-480 V, IP21, IE2, Frame R1, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3.0 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Output Current, Light-Overload Use (IlD)":"8.9 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048684-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048684-D/alternatives.json"},"ai":{"faq":[{"question":"What is the difference between normal-use and heavy-duty ratings on this drive?","answer":"Normal-use rating is 4 kW / 9.4 A for variable-torque loads; heavy-duty rating is 3.0 kW / 7.2 A for constant-torque loads. The heavy-duty figure is the one to use when sizing for conveyors or positive-displacement pumps."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048684-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048684-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}