{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048694-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048694-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048694-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048694-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-106A-4, 3ABD00048694-D, LV AC general-purpose wall-mounted drive, 380–480 V, 55 kW / 106 A normal use, IP21, NEMA Type 1, Frame R5.","salesMarkdown":"## Drive selection memo – 55 kW class, wall-mount The ABB 3ABD00048694-D is a general-purpose LV AC wall-mounted drive rated for 55 kW normal use at 106 A, with a 380–480 V three-phase input. It carries an IE2 efficiency level and an IP21 / NEMA Type 1 enclosure. ## Heavy-duty vs normal-use headroom The drive carries two duty ratings: 55 kW / 106 A for normal use, and 45 kW / 87 A for heavy-duty use. If your load profile includes sustained overloads or high starting torque, size against the heavy-duty numbers — that 87 A continuous is the line for constant-torque applications like conveyors or extruders. ## Installation notes Wall-mounted only — no flange kit or floor-standing adapter in this order code. The IP21 / NEMA 1 enclosure suits clean, dry indoor environments.","metaTitle":"ABB 3ABD00048694-D ACS580-01-106A-4, 55 kW LV AC Drive, IP21","metaDescription":"ABB ACS580-01-106A-4 general-purpose wall-mounted drive. 55 kW normal use, 106 A output, IP21, NEMA 1, IE2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R5","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"55 kW","Output Current, Normal Use (In)":"106 A","Output Power, Heavy-Duty Use (PhD)":"45 kW","Output Current, Heavy-Duty Use (IhD)":"87 A","Output Power, Light-Overload Use (PlD)":"55 kW","Output Current, Light-Overload Use (IlD)":"100 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048694-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048694-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R5 — that determines the mounting footprint and the available options slot layout."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal use: 55 kW / 106 A. Heavy-duty use: 45 kW / 87 A. Light-overload use: 55 kW / 100 A."},{"question":"What enclosure protection does this drive have?","answer":"IP21 with NEMA Type 1 enclosure — suitable for indoor, dry locations where dripping water and falling dirt are the main hazards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048694-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048694-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}