{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048740-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048740-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048740-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048740-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted LV AC drive, 55 kW normal-use output, 106 A, 380-480 V 3-phase, IP21, IE2, frame size R5.","salesMarkdown":"The ABB 3ABD00048740-D is an ACQ580-01 series wall-mounted drive rated for 55 kW normal use at 106 A, 380-480 V three-phase input. It's built for water and wastewater applications, with IE2 efficiency and an IP21 enclosure that keeps out drips and dust in a pump house or treatment plant. The normal-use rating of 55 kW and 106 A is the continuous duty point for a typical centrifugal pump or fan load. Heavy-duty use drops to 45 kW and 87 A — that's the rating you spec for a positive-displacement pump or a conveyor with high starting torque. Light-overload use sits at 55 kW and 100 A, a middle ground for applications with occasional overloads but not constant high torque. The drive accepts 380-480 V three-phase and runs on 47.5-63 Hz supply, so it handles 50 Hz and 60 Hz grids without a transformer swap. Frame size R5 means it's a compact wall-mount unit, not a floor-standing cabinet — good for retrofitting into existing panel space. The wall-mounted enclosure carries a NEMA Type 1 rating (indoor use, no falling dirt or dripping water) and IP21 protection (fingers and vertical drips). That's standard for a clean, dry pump room or treatment building. If the drive needs to live outdoors or in a washdown area, you'd step up to a higher IP or add a separate enclosure.","metaTitle":"ABB 3ABD00048740-D ACQ580-01 Drive, 55 kW, 106 A, IP21","metaDescription":"ABB 3ABD00048740-D ACQ580-01 wall-mounted drive, 55 kW normal use, 106 A output, 380-480 V, IP21, IE2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R5","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"55 kW","Output Current, Normal Use (In)":"106 A","Output Power, Heavy-Duty Use (PhD)":"45 kW","Output Current, Heavy-Duty Use (IhD)":"87 A","Output Power, Light-Overload Use (PlD)":"55 kW","Output Current, Light-Overload Use (IlD)":"100 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048740-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048740-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 55 kW at 106 A; heavy-duty output is 45 kW at 87 A; light-overload output is 55 kW at 100 A. Input is 380-480 V three-phase, 47.5-63 Hz. Efficiency is IE2, enclosure is IP21/NEMA Type 1, frame size R5."},{"question":"How do I source this drive?","answer":"This is an active, current-production part. Submit an RFQ with your quantity and delivery requirements; we'll quote against the order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048740-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048740-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}