{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048745-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048745-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048745-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048745-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted LV AC drive, 3ABD00048745-D, 160 kW normal-duty / 132 kW heavy-duty, 293 A / 246 A, 380-480 V, IP21, IE2.","salesMarkdown":"The ABB 3ABD00048745-D is an ACQ580-01 wall-mounted LV AC drive, sized for water and wastewater applications. It delivers 160 kW in normal use (293 A) and 132 kW in heavy-duty use (246 A), running on 380...480 V three-phase input at 47.5...63 Hz. Frame size R8, IP21 enclosure, NEMA Type 1, and IE2 efficiency class. Three duty ratings are on the nameplate: normal-use (Pn 160 kW, In 293 A), heavy-duty (PhD 132 kW, IhD 246 A), and light-overload (PlD 160 kW, IlD 278 A). The 246 A heavy-duty current is 16 % lower than the normal-use figure — that delta matters when the motor is oversized or the cycle includes a high starting torque.","metaTitle":"ABB 3ABD00048745-D ACQ580-01 Wall-Mounted Drive, 160 kW, 293","metaDescription":"ABB ACQ580-01-293A-4+X1666+N7560 wall-mounted LV AC drive, 160 kW normal use, 293 A output, IP21, IE2, 380-480 V, 3-phase. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"160 kW","Output Current, Normal Use (In)":"293 A","Output Power, Heavy-Duty Use (PhD)":"132 kW","Output Current, Heavy-Duty Use (IhD)":"246 A","Output Power, Light-Overload Use (PlD)":"160 kW","Output Current, Light-Overload Use (IlD)":"278 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048745-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048745-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00048745-D?","answer":"Frame size R8."},{"question":"What is the input frequency range?","answer":"47.5 to 63 Hz."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal use: 160 kW, 293 A. Heavy-duty use: 132 kW, 246 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048745-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048745-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}