{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00048858-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00048858-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00048858-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00048858-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-039A-4+J404, general-purpose wall-mounted drive, 18.5 kW / 38 A normal use, 380-500 V 3-phase input, IP21, IE2, frame R3.","salesMarkdown":"The ABB 3ABD00048858-D is a general-purpose wall-mounted LV AC drive from the ACS580-01 family, rated for 18.5 kW normal-use output at 38 A and 15 kW heavy-duty output at 31.6 A. It accepts 380-500 V three-phase input and covers 47.5 to 63 Hz. The IP21 enclosure and NEMA Type 1 rating suit it for clean indoor environments; frame size R3 keeps the footprint manageable for panel layouts where wall-mounting is preferred. ## Load ratings and duty selection The normal-use rating (18.5 kW, 38 A) covers constant-torque loads like conveyors and fans at 100 % duty cycle. Light-overload use is spec'd at 18.5 kW and 36.1 A, which matches the normal-use power but at slightly lower current, indicating a different thermal model for variable-torque loads. The IE2 efficiency level keeps losses in check for continuous operation.","metaTitle":"ABB 3ABD00048858-D ACS580-01-039A-4+J404 Drive, 18.5 kW, 38","metaDescription":"ABB 3ABD00048858-D ACS580-01-039A-4+J404 general-purpose drive, 18.5 kW normal use, 38 A output, 380-500 V 3-phase input, IP21, IE2, frame R3, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R3","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"18.5 kW","Output Current, Normal Use (In)":"38 A","Output Power, Heavy-Duty Use (PhD)":"15 kW","Output Current, Heavy-Duty Use (IhD)":"31.6 A","Output Power, Light-Overload Use (PlD)":"18.5 kW","Output Current, Light-Overload Use (IlD)":"36.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00048858-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00048858-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 18.5 kW at 38 A; heavy-duty output is 15 kW at 31.6 A. Input is 380-500 V three-phase, 47.5-63 Hz. Enclosure is IP21 / NEMA Type 1, frame size R3, wall-mounted."},{"question":"What efficiency class does this drive meet?","answer":"It is rated IE2 efficiency."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00048858-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00048858-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}