{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00049860","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00049860","canonicalUrl":"https://aoctrl.com/abb/3ABD00049860","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00049860","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ531-01-246A-4+0J404 drive, 132 kW, 246 A, 380-480 V, IP20, Frame R8, wall-mounted.","salesMarkdown":"The 3ABD00049860: The ABB ACQ531-01-246A-4+0J404 is an R8-frame drive rated for 132 kW output power at 246 A in normal use, with a 380-480 V three-phase input. The light-overload rating holds at 132 kW / 234 A, so the drive is sized for continuous-duty centrifugal loads — pumps, fans, compressors — where the motor nameplate matches the normal-use current. Wall-mounted, IP20, open type enclosure; expect to install it in a clean, ventilated cabinet or dedicated drive room. The 246 A normal-use output current (In) is the figure that governs motor sizing for continuous duty — pair it with a motor whose full-load amps sit at or below that number. The light-overload current (IlD) of 234 A is the same power rating, so the drive does not offer a higher short-term overload headroom; it is a constant-torque-rated unit. Input frequency range of 47.5 to 63 Hz covers both 50 Hz and 60 Hz grids without derating. IE2 efficiency level means the drive meets the minimum efficiency standard for that class, not premium efficiency. ## Mounting and compliance notes Wall-mounted, IP20, open type — plan for top and bottom cable entry with clearance for the R8 frame's heat sink airflow. WEEE category 5 (small equipment under 50 cm) governs end-of-life disposal in EU markets; no RoHS/REACH statement is carried in this listing, so verify local compliance documentation separately if required.","metaTitle":"3ABD00049860 ABB ACQ531-01-246A-4+0J404, 132 kW, 246 A, Fram","metaDescription":"ABB ACQ531-01-246A-4+0J404 drive, 132 kW output power, 246 A output current, 380-480 V input, IP20, wall-mounted, IE2, active lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"246 A","Output Power, Light-Overload Use (PlD)":"132 kW","Output Current, Light-Overload Use (IlD)":"234 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00049860","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00049860/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R8."},{"question":"What input voltage and frequency does it accept?","answer":"380-480 V three-phase, 47.5 to 63 Hz."},{"question":"What is the output power and current rating?","answer":"132 kW output power, 246 A normal-use output current (In), 234 A light-overload current (IlD)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00049860","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00049860 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}