{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00049991-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00049991-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00049991-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00049991-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS530-01-07A2-4+P973, 3 kW, 7.2 A, 380-500 V, IP20, IE2.","salesMarkdown":"The ABB 3ABD00049991-D is an ACS530-01-07A2-4+P973 variable frequency drive rated for 3 kW normal-use output power and 7.2 A output current, fed from a 380-500 V three-phase supply. It carries an IE2 efficiency classification and mounts in an IP20 open-type enclosure, frame size R0. The 7.2 A normal-use current (In) is the figure to size motor cables and branch protection against — that's the continuous rating at the drive's full switching frequency. Light-overload duty drops to 6.8 A (IlD), which still covers most constant-torque applications below 3 kW. ## Installation notes Wall-mounted, IP20 — plan for a clean, dry cabinet with clearance around the heatsink fins. Frame R0 keeps the footprint compact; verify gland-plate access for the incoming 3-phase and motor cables. The open-type NEMA enclosure means no additional environmental sealing inside the panel.","metaTitle":"ABB 3ABD00049991-D ACS530-01-07A2-4+P973, 3 kW VFD","metaDescription":"ABB ACS530-01-07A2-4+P973 (3ABD00049991-D) 3 kW VFD, 7.2 A output, 380-500 V input, IP20, IE2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R0","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"3 kW","Output Current, Normal Use (In)":"7.2 A","Output Power, Light-Overload Use (PlD)":"3 kW","Output Current, Light-Overload Use (IlD)":"6.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00049991-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00049991-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R0."},{"question":"What input voltage and frequency does it accept?","answer":"380-500 V three-phase, 47.5-63 Hz."},{"question":"What is the output power and current rating?","answer":"3 kW normal-use output power, 7.2 A normal-use output current. Light-overload rating is 3 kW at 6.8 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00049991-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00049991-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}