{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00050162-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00050162-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00050162-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00050162-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-04 general purpose drive module, 3ABD00050162-D, 380-500 VAC 3-phase, 250 kW / 505 A normal use, IP00, frame size R10, IE2.","salesMarkdown":"The 3ABD00050162-D is an ABB ACS580-04 LV AC general purpose drive module, rated for 250 kW normal-use output at 505 A, with a heavy-duty rating of 200 kW at 361 A. It accepts 380-500 VAC three-phase input at 47.5-63 Hz and is built in frame size R10, IP00 open-type enclosure. Efficiency class is IE2. The heavy-duty curve drops to 361 A at 200 kW — that's the number to check if the motor is cycled hard or runs in a high ambient. Frame R10 and IP00 mean it's a chassis mount for a cabinet; no conduit box, no touch-safe cover. ## Integration Notes Three-phase input only. Frequency range 47.5-63 Hz covers 50/60 Hz mains. Open-type enclosure requires the panel builder to provide separation and cooling — no derating for IP00, but the heat sink needs free air. WEEE category 4 means end-of-life take-back applies in EU jurisdictions.","metaTitle":"ABB 3ABD00050162-D ACS580-04 Drive Module, 250 kW, 505 A","metaDescription":"ABB ACS580-04 drive module, 250 kW normal use, 505 A output, 380-500 VAC 3-phase, IP00, frame R10. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R10","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP00","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"505 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"361 A","Output Power, Light-Overload Use (PlD)":"250 kW","Output Current, Light-Overload Use (IlD)":"485 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00050162-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00050162-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size R10."},{"question":"What input voltage and frequency does it accept?","answer":"380-500 VAC three-phase at 47.5-63 Hz."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal use: 250 kW at 505 A. Heavy-duty use: 200 kW at 361 A. Light-overload use: 250 kW at 485 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00050162-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00050162-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}