{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00050269-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00050269-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00050269-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00050269-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS530-01-206A-4+N7569, frame size R7, 110 kW output, 206 A normal use, 380-480 V 3-phase input, IP20, wall-mounted.","salesMarkdown":"The ABB 3ABD00050269-D is an ACS530-01-206A-4+N7569 drive in frame size R7, rated for 110 kW normal-use output and 206 A continuous current on a 380-480 V three-phase supply. It is wall-mounted with IP20 protection and carries an IE2 efficiency classification. The 206 A normal-use current (In) is the figure to size motor cables and upstream protection against — that is the continuous rating at the drive output. Light-overload duty drops to 196 A (IlD), still at 110 kW, which gives headroom for short-duration overloads on pumps or fans without oversizing the drive frame. Input frequency range of 47.5-63 Hz covers 50/60 Hz grids globally.","metaTitle":"ABB 3ABD00050269-D ACS530-01-206A-4+N7569, 110 kW, 206 A","metaDescription":"ABB ACS530-01-206A-4+N7569 drive, 110 kW output, 206 A normal use, 380-480 V 3-phase input, IP20, wall-mounted, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R7","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"206 A","Output Power, Light-Overload Use (PlD)":"110 kW","Output Current, Light-Overload Use (IlD)":"196 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00050269-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00050269-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R7."},{"question":"What input voltage and frequency does it accept?","answer":"Three-phase 380-480 V at 47.5-63 Hz."},{"question":"What is the output power and current rating?","answer":"110 kW normal-use output at 206 A continuous; light-overload rating is 110 kW at 196 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00050269-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00050269-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}