{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00050561","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00050561","canonicalUrl":"https://aoctrl.com/abb/3ABD00050561","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00050561","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380 machinery drive module, 3ABD00050561, Frame R1, 4 kW normal-use / 3 kW heavy-duty, 9.4 A / 7.2 A, 380–480 V 3-phase, IP20.","salesMarkdown":"## Output ratings — normal vs heavy duty The 3ABD00050561: Two duty ratings let you match the drive to the load profile. Normal-use (Pn 4 kW, 9.4 A) covers constant-torque applications like conveyors and pumps. Heavy-duty (PhD 3 kW, 7.2 A) handles higher overloads — mixers, crushers, or frequent start/stop cycles. The light-overload rating (PlD 4 kW, 8.9 A) sits between them, useful for variable-torque loads like fans. Frame R1 determines mounting footprint and panel cutout. IP20 allows installation in a clean, dry enclosure — not rated for washdown or dust. Open-type NEMA enclosure means it requires an upstream protective device for branch-circuit protection. 380–480 V input covers common 400 V and 480 V industrial supplies worldwide.","metaTitle":"ABB 3ABD00050561 ACS380 Drive Module, 4 kW, 9.4 A, Frame R1","metaDescription":"ABB 3ABD00050561 ACS380-040C-09A4-4 drive module, 4 kW normal-use output, 9.4 A, 380–480 V, 3-phase, IP20, Frame R1. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"8.9 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00050561","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00050561/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00050561?","answer":"Frame R1. This determines the physical mounting dimensions and panel cutout for the drive module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00050561","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00050561 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}