{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00057690-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00057690-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00057690-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00057690-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 series LV AC industrial drive, 3ABD00057690-D, 132 kW / 246 A normal duty, 110 kW heavy duty, frame R8, IP21, IE2, wall-mounted.","salesMarkdown":"## Ratings and fit for the application The 3ABD00057690-D: Frame size R8 dictates the physical envelope, wall-mount bracket pattern, and cable-entry positions. Verify that your gland plate and the R8 cut-out match before ordering the backplate. IP21 enclosure limits the drive to indoor, non-hosedown areas; if your cooling air contains conductive dust, step up to IP54. Input voltage tolerance 380–415 V three-phase covers standard low-voltage grids. Paralleling multiple drives on the same bus requires line reactors per ABB's harmonic mitigation note—this drive has no built-in DC choke.","metaTitle":"ABB 3ABD00057690-D ACS880-01 Drive, 132 kW","metaDescription":"Active-production ABB ACS880-01 wall-mounted drive, 132 kW / 246 A normal duty, 110 kW heavy duty, frame R8, IP21, IE2. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"246 A","Output Power, Heavy-Duty Use (PhD)":"110 kW","Output Current, Heavy-Duty Use (IhD)":"206 A","Output Power, Light-Overload Use (PlD)":"132 kW","Output Current, Light-Overload Use (IlD)":"234 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00057690-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00057690-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R8. This physically determines the wall-mount cut-out dimensions, cable entry locations, and gland plate pattern—verify against your panel layout before ordering."},{"question":"What are the key power and current ratings?","answer":"Normal duty: 132 kW at 246 A continuous. Heavy duty: 110 kW at 206 A for overload-prone loads. Light-overload use is rated at 132 kW and 234 A (the normal-duty current is the limiting factor)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00057690-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00057690-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}