{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00057775","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00057775","canonicalUrl":"https://aoctrl.com/abb/3ABD00057775","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00057775","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380-040C-038A-4+X1607+L535, LV AC machinery drive module, 18.5 kW / 38.0 A normal use, 380-480 V 3-phase, IP20, frame size R4.","salesMarkdown":"The ABB 3ABD00057775 is an ACS380-series machinery drive module in frame size R4, rated for 18.5 kW normal use at 38.0 A continuous output on a 380–480 V three-phase supply. Heavy-duty use drops to 15.0 kW and 32.0 A; light-overload use holds at 18.5 kW but current limits to 36.0 A. The IP20 open-type enclosure is sized for cabinet mounting, not standalone washdown areas. The 38.0 A normal-use current (In) is the continuous rating for a standard 18.5 kW motor load at 400 V. If your application involves frequent overloads or constant torque below base speed, the heavy-duty curve (32.0 A, 15.0 kW) is the one that governs thermal capacity — don't size against the normal-use number for a crusher or extruder duty. The IE2 efficiency level is baseline for this class; it's not premium efficiency, but it's adequate for most constant-torque pumps and fans. ## Integration notes The module accepts 47.5–63 Hz input, covering 50 Hz and 60 Hz grids globally. Frame R4 determines the mounting footprint and bus-bar layout — verify panel cutout dimensions against the ACS380 mechanical drawing before cutting the backplate. The IP20 rating means the drive needs a clean, dry cabinet; no washdown or dust-tight installation without an additional enclosure.","metaTitle":"ABB 3ABD00057775 ACS380 Drive Module, 18.5 kW, 38 A, IP20","metaDescription":"ABB 3ABD00057775 ACS380 drive module, 18.5 kW normal use, 38.0 A output, 380-480 V, IP20, frame R4. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R4","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"18.5 kW","Output Current, Normal Use (In)":"38.0 A","Output Power, Heavy-Duty Use (PhD)":"15.0 kW","Output Current, Heavy-Duty Use (IhD)":"32.0 A","Output Power, Light-Overload Use (PlD)":"18.5 kW","Output Current, Light-Overload Use (IlD)":"36.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00057775","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00057775/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R4. This determines the physical mounting dimensions and bus-bar connections for the module."},{"question":"What are the normal-use and heavy-duty current ratings?","answer":"Normal use: 38.0 A continuous (18.5 kW). Heavy-duty use: 32.0 A (15.0 kW). Light-overload use: 36.0 A (18.5 kW). Use the heavy-duty rating for constant-torque or high-overload applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00057775","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00057775 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}