{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00058727-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00058727-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00058727-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00058727-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531 HVAC drive, 3ABD00058727-D, 75 kW, 145 A, R6 frame, IP20, 380-500 V, 3-phase.","salesMarkdown":"The ABB 3ABD00058727-D is an ACH531 series low-voltage AC wall-mounted drive built for HVAC duty. It delivers 75 kW output power at 145 A normal-use current, fed from a 380-500 V, 3-phase supply at 47.5-63 Hz. Frame size R6 with an IP20 open-type NEMA enclosure means it's meant for clean indoor panel or machine-mount — not washdown or dust-heavy areas. The 75 kW normal-use power and 145 A output current are the numbers that govern motor sizing — match these to your fan or pump full-load amps, not the motor nameplate kW alone. Light-overload rating sits at 138 A, so if your load profile includes intermittent overloads, that's the ceiling. The 380-500 V input range covers common 400 V and 480 V grids; the 47.5-63 Hz frequency acceptance handles 50/60 Hz without a configuration change. Frame R6 is a physical size — verify the mounting footprint against your existing panel layout; wall-mount means no floor stand needed, but IP20 requires a clean environment or an additional enclosure.","metaTitle":"ABB 3ABD00058727-D ACH531 HVAC Drive, 75 kW, 145 A, R6","metaDescription":"ABB 3ABD00058727-D ACH531 HVAC drive, 75 kW output, 145 A normal use, R6 frame, IP20, 380-500 V, 47.5-63 Hz. Active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00058727-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00058727-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00058727-D?","answer":"It is an R6 frame. That determines physical mounting dimensions, gland plate clearance, and bus bar or cable lug sizing for the power terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00058727-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00058727-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}