{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00058757-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00058757-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00058757-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00058757-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 single drive module, 3-phase 380-415 V, 315 kW / 585 A normal use, 250 kW / 429 A heavy duty, IP20, frame R10.","salesMarkdown":"The ABB 3ABD00058757-D is an ACS880-04 liquid-cooled single drive module rated for 315 kW normal use at 585 A on a 380-415 V three-phase supply, with a heavy-duty curve at 250 kW / 429 A and a light-overload rating of 315 kW / 575 A. Frame size R10, IP20 open-type enclosure. Efficiency class IE2. Frequency range 47.5 to 63 Hz covers 50/60 Hz grids without derating. The 585 A normal-use current (Pn 315 kW) is the continuous rating for typical industrial loads with 110% overload for 1 minute every 10 minutes. The heavy-duty curve at 429 A (250 kW) supports 150% overload for 1 minute — use this for high-start-torque applications like conveyors or crushers. The light-overload rating at 575 A (315 kW) matches the normal-use power but with a lower current limit, useful when the motor's thermal capacity is the constraint. IP20 means the module requires installation inside a cabinet or enclosure; it is not stand-alone rated for dust or washdown. ## Integration notes Mounts as a module — frame R10 dictates the physical footprint and busbar layout. Three-phase input at 380-415 V, 47.5-63 Hz. Open-type enclosure means the drive relies on the cabinet's airflow for cooling; verify fan capacity and ambient temperature limits from the ACS880-04 hardware manual. The liquid-cooled variant rejects heat to a coolant loop, not to the cabinet air, so plan for a cooling circuit with the correct flow rate and coolant type.","metaTitle":"ABB 3ABD00058757-D ACS880-04 drive module, 315 kW, 585 A","metaDescription":"Active ABB ACS880-04 single drive module, 3-phase, 380-415 V, 315 kW normal use (585 A), 250 kW heavy duty (429 A), IP20, frame R10. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R10","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"315 kW","Output Current, Normal Use (In)":"585 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"429 A","Output Power, Light-Overload Use (PlD)":"315 kW","Output Current, Light-Overload Use (IlD)":"575 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00058757-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00058757-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"The frame size is R10, which determines the mounting dimensions and busbar connections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00058757-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00058757-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}