{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00058810-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00058810-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00058810-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00058810-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880 LV AC machinery drive module, 3ABD00058810-D, frame size R2, 4 kW normal-use output, 10.5 A, 380-480 V 3-phase, IP20, Open Type.","salesMarkdown":"The ABB 3ABD00058810-D is an ACS880-series LV AC machinery drive module with integrated position control, rated for 4 kW normal-use output at 10.5 A on a 380-480 V 3-phase supply. Frame size R2, IP20, Open Type enclosure — sized for a standard cabinet mount without additional enclosure protection. Three duty ratings are listed: normal use (Pn 4 kW, In 10.5 A), heavy-duty (PhD 4 kW, IhD 9 A), and light-overload (PlD 4 kW, IlD 9.7 A). All three converge on the same 4 kW power figure, so the drive is sized for a constant-power motor load up to that output — the current difference between duty classes reflects the thermal headroom for varying overload profiles. For a 4 kW motor on a constant-torque application, the normal-use current of 10.5 A is the spec to match against the motor nameplate. Input voltage covers 380-480 V at 48-63 Hz, which covers 50 Hz and 60 Hz mains without derating. The 3-phase input is standard for this power class.","metaTitle":"ABB 3ABD00058810-D ACS880 Drive Module, 4 kW, 10.5 A, R2","metaDescription":"ABB 3ABD00058810-D ACS880 LV AC drive module, 4 kW normal use, 10.5 A, frame size R2, IP20, 380-480 V, 3-phase. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R2","Frequency (f)":"48 ... 63 Hz","Mounting Type":"Module","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"10.5 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"9 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"9.7 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00058810-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00058810-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size R2. That determines the physical footprint and mounting hole pattern for cabinet layout."},{"question":"What are the key electrical ratings for this drive?","answer":"Normal-use output: 4 kW at 10.5 A. Heavy-duty: 4 kW at 9 A. Light-overload: 4 kW at 9.7 A. Input: 380-480 V, 48-63 Hz, 3-phase."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00058810-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00058810-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}