{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059524-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059524-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059524-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059524-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB 3ABD00059524-D, ACS880-01 series, LV AC industrial wall-mounted single drive, R2 frame, 7.5 kW normal-duty output at 14 A, 380–500 VAC 3-phase, IE2, IP21, Type 1 enclosure.","salesMarkdown":"The ABB 3ABD00059524-D is a wall-mounted single drive for 3-phase LV AC induction motors. Its normal-duty rating is 7.5 kW at 14 A; heavy-duty mode derates to 5.5 kW at 11 A. Light-overload use stays at 7.5 kW, 13 A. Input voltage range is 380 to 500 VAC, 47.5 to 63 Hz. The R2 frame keeps the footprint compact for a 7.5 kW unit; wall-mount it with the IP21 / NEMA Type 1 enclosure. ## Normal vs heavy-duty — pick the right column The dual rating matters more than the headline kW. Normal duty (7.5 kW, 14 A) is for variable-torque loads. Heavy-duty (5.5 kW, 11 A) is the constant-torque ceiling — match that to your motor nameplate if the load profile includes starting torque or short-term overloads. Sizing against the normal-duty figure alone risks a drive that trips on a conveyor start.","metaTitle":"ABB 3ABD00059524-D ACS880-01 Drive, 7.5 kW, 14 A, R2","metaDescription":"ABB 3ABD00059524-D ACS880-01 LV AC wall-mounted drive, 7.5 kW / 14 A normal duty, 5.5 kW / 11 A heavy duty, R2 frame, IP21, Type 1, 380-500 V, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"7.5 kW","Output Current, Normal Use (In)":"14 A","Output Power, Heavy-Duty Use (PhD)":"5.5 kW","Output Current, Heavy-Duty Use (IhD)":"11 A","Output Power, Light-Overload Use (PlD)":"7.5 kW","Output Current, Light-Overload Use (IlD)":"13 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059524-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059524-D/alternatives.json"},"ai":{"faq":[{"question":"What are the normal-duty and heavy-duty ratings?","answer":"Normal duty: 7.5 kW, 14 A. Heavy-duty: 5.5 kW, 11 A. Light-overload (variable torque) is 7.5 kW, 13 A."},{"question":"What is the frame size and enclosure?","answer":"R2 frame, wall-mounted, IP21 ingress protection, NEMA Type 1 enclosure."},{"question":"What input voltage and frequency does it accept?","answer":"380 to 500 VAC, 3-phase, 47.5 to 63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059524-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059524-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}