{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059544-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059544-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059544-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059544-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 LV AC wall-mounted single drive, 3-phase, 380...500 V, 90 kW / 156 A normal use, IP21, NEMA Type 1, frame size R7.","salesMarkdown":"The ABB 3ABD00059544-D is an ACS880-01 LV AC industrial wall-mounted single drive, rated for 90 kW normal-use output at 156 A on a 380...500 V three-phase supply. It carries a heavy-duty rating of 75 kW at 124 A and a light-overload rating of 90 kW at 148 A, giving you three distinct duty curves to match the load profile — normal use for constant-torque applications, heavy-duty for high-starting-torque loads, and light-overload for variable-torque fans or pumps where the drive can run slightly above its continuous rating without tripping. The heavy-duty curve at 124 A applies when the motor demands higher starting torque or short-term overloads, typical of crushers or extruders. The light-overload curve at 148 A covers variable-torque loads like centrifugal fans or pumps where the drive can deliver 90 kW continuously but the motor current stays below the 156 A normal-use ceiling. All three ratings are verified at the drive's rated frequency range of 47.5...63 Hz, so the drive handles 50 Hz and 60 Hz grids without derating. Wall-mounted in an IP21 enclosure with a NEMA Type 1 rating — suitable for indoor installation where dripping water or falling dirt is not a concern. The frame size is R7, which determines the physical footprint and gland-plate layout. The NEMA Type 1 rating confirms it meets the standard for indoor enclosures with no additional environmental protection.","metaTitle":"ABB 3ABD00059544-D ACS880-01 Drive, 90 kW, 156 A, IP21","metaDescription":"ABB 3ABD00059544-D ACS880-01 LV AC drive, 90 kW normal use, 156 A, IP21, wall-mounted, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R7","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"90 kW","Output Current, Normal Use (In)":"156 A","Output Power, Heavy-Duty Use (PhD)":"75 kW","Output Current, Heavy-Duty Use (IhD)":"124 A","Output Power, Light-Overload Use (PlD)":"90 kW","Output Current, Light-Overload Use (IlD)":"148 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059544-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059544-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00059544-D?","answer":"The frame size is R7, which determines the physical mounting dimensions and gland-plate layout."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal use: 90 kW at 156 A. Heavy-duty use: 75 kW at 124 A. Light-overload use: 90 kW at 148 A."},{"question":"What is the enclosure protection rating?","answer":"IP21 with a NEMA Type 1 rating, suitable for indoor wall-mounted installation where dripping water or falling dirt is not a concern."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059544-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059544-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}