{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059546-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059546-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059546-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059546-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 LV AC industrial wall-mounted single drive, Frame R8, 132 kW normal use, 240 A output, IP21, IE2.","salesMarkdown":"The ABB 3ABD00059546-D is an ACS880-01 series LV AC industrial wall-mounted single drive, Frame R8, rated for 132 kW normal-use output at 240 A. ## Sizing and duty ratings Three duty points are listed: normal use (132 kW, 240 A), light-overload (132 kW, 228 A), and heavy-duty (110 kW, 180 A). The heavy-duty current is the one to hold for sizing against a constant-torque load profile — the 180 A figure is what governs thermal capacity under sustained high torque. ## Physical and environmental Wall-mounted enclosure, NEMA Type 1, IP21. Rated for 47.5...63 Hz supply. Efficiency class IE2. The IP21 rating means it is suitable for clean indoor environments with no falling water or dust ingress — typical for a panel or machine-mounted installation.","metaTitle":"ABB 3ABD00059546-D ACS880-01 Drive, 132 kW, 240 A, Frame R8","metaDescription":"ABB ACS880-01 wall-mounted drive, 132 kW normal use, 240 A output, IP21, IE2 efficiency, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"240 A","Output Power, Heavy-Duty Use (PhD)":"110 kW","Output Current, Heavy-Duty Use (IhD)":"180 A","Output Power, Light-Overload Use (PlD)":"132 kW","Output Current, Light-Overload Use (IlD)":"228 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059546-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059546-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00059546-D?","answer":"Frame size R8. This determines mounting dimensions and physical footprint for panel layout."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059546-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059546-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}