{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059547-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059547-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059547-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059547-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01, 3ABD00059547-D, wall-mounted LV AC drive, 160 kW normal use, 260 A, 380-500 V, 3-phase, IP21, NEMA 1, IE2, frame R8.","salesMarkdown":"The ABB 3ABD00059547-D is a wall-mounted LV AC drive rated for 160 kW normal use at 260 A, with a 380-500 V three-phase input. It carries a NEMA Type 1 enclosure and IP21 protection. The drive lists three duty points: normal use at 160 kW / 260 A, heavy-duty at 132 kW / 240 A, and light-overload at 160 kW / 247 A. For a constant-torque load like a conveyor or positive-displacement pump, the heavy-duty figure governs — you get 132 kW continuous. For variable-torque (centrifugal fans, pumps), the normal-use 160 kW applies. The light-overload column is a short-time rating, not continuous; use it for starting or intermittent peak loads. Wall-mounted in a NEMA 1 / IP21 enclosure — no conduit knockouts for top entry, so plan for bottom cable glanding. Frame size R8; that's a larger footprint, so verify your backplate layout before cutting the gland plate. The drive is 3-phase input only, no single-phase option.","metaTitle":"ABB 3ABD00059547-D ACS880-01 Drive, 160 kW, 260 A, IP21","metaDescription":"ABB ACS880-01 wall-mounted drive, 160 kW normal use, 260 A, 380-500 V, IP21, NEMA 1, IE2. Active production, frame R8. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"160 kW","Output Current, Normal Use (In)":"260 A","Output Power, Heavy-Duty Use (PhD)":"132 kW","Output Current, Heavy-Duty Use (IhD)":"240 A","Output Power, Light-Overload Use (PlD)":"160 kW","Output Current, Light-Overload Use (IlD)":"247 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059547-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059547-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R8."},{"question":"What is the input voltage and frequency range?","answer":"380-500 V three-phase, 47.5-63 Hz."},{"question":"What is the normal-use output rating?","answer":"160 kW at 260 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059547-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059547-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}