{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059562-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059562-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059562-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059562-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01, LV AC industrial wall-mounted single drive with position control, 110 kW / 119 A normal duty, 525–690 V 3-phase, IP21, R7 frame.","salesMarkdown":"The ABB 3ABD00059562-D is a wall-mounted LV AC drive for 3-phase induction motors with position control onboard. Rated for 110 kW normal duty (119 A) and 90 kW heavy duty (98 A), so you size it to the motor nameplate, not the maximum. Input voltage spans 525 to 690 V, 48 to 63 Hz — common for 690 V industrial grids in mining or marine. The IP21 enclosure keeps out fingers and dripping water, but it's Open Type per NEMA, so it belongs in a clean panel, not out on a washdown floor. Frame size R7 tells you the physical footprint and the bus-bar layout. If you're swapping into an existing cabinet, measure the mounting hole pattern and the gland-plate area — R7 is a specific bolt pattern that won't match R6 or R8. Light-overload rating matches the normal-duty figure at 110 kW (113 A), so if your load profile is mostly steady-state with short peaks, you don't lose headroom. Heavy-duty is the tighter number for applications that cycle hard.","metaTitle":"ABB 3ABD00059562-D ACS880-01 Drive, 110 kW, 119 A","metaDescription":"ABB ACS880-01 wall-mounted drive, 110 kW normal duty, 119 A, 525–690 V input, IP21, R7 frame, active production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Frame Size":"R7","Frequency (f)":"48 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"525 ... 690 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"119 A","Output Power, Heavy-Duty Use (PhD)":"90 kW","Output Current, Heavy-Duty Use (IhD)":"98 A","Output Power, Light-Overload Use (PlD)":"110 kW","Output Current, Light-Overload Use (IlD)":"113 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059562-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059562-D/alternatives.json"},"ai":{"faq":[{"question":"What frame size is this drive?","answer":"It's an R7 frame. That determines the physical mounting and bus-bar layout for panel integration."},{"question":"What are the normal-duty and heavy-duty ratings?","answer":"Normal duty is 110 kW / 119 A; heavy duty is 90 kW / 98 A. The heavy-duty figure is the one to use for constant-torque loads."},{"question":"What input voltage and frequency does it accept?","answer":"It accepts 525–690 V AC, 48–63 Hz, 3-phase. That covers standard 690 V industrial grids."},{"question":"What is the enclosure protection rating?","answer":"IP21, which is finger-safe and drip-proof. It's also classified as NEMA Open Type, so install it inside a clean panel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059562-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059562-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}