{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059566-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059566-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059566-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059566-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 LV AC industrial wall-mounted single drive, 3-phase, 525-690 V, 30 kW / 35 A normal use, frame size R5, IP21, NEMA Open Type.","salesMarkdown":"The ABB 3ABD00059566-D is an ACS880-01 wall-mounted drive rated for 30 kW normal use at 35 A, with heavy-duty use rated at 22 kW and 26 A. It accepts a 525 to 690 V three-phase input across 48 to 63 Hz and carries IP21 protection in a NEMA Open Type enclosure. Frame size is R5. The normal-use rating of 30 kW and 35 A is the continuous output for typical pump, fan, or conveyor loads. Heavy-duty use at 22 kW and 26 A applies when the drive must handle higher peak torque or constant torque loads — extruders, crushers, or hoists. Light-overload use at 30 kW and 33 A sits between the two, covering applications with occasional overload cycles. The 525-690 V input range suits 690 V industrial networks common in European and marine installations.","metaTitle":"ABB 3ABD00059566-D ACS880-01 Drive, 30 kW, 35 A, R5","metaDescription":"ABB ACS880-01 drive, 30 kW normal use, 35 A, 525-690 V, 3-phase, IP21, wall-mounted, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Frame Size":"R5","Frequency (f)":"48 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"525 ... 690 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"30 kW","Output Current, Normal Use (In)":"35 A","Output Power, Heavy-Duty Use (PhD)":"22 kW","Output Current, Heavy-Duty Use (IhD)":"26 A","Output Power, Light-Overload Use (PlD)":"30 kW","Output Current, Light-Overload Use (IlD)":"33 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059566-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059566-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal use: 30 kW, 35 A. Heavy-duty use: 22 kW, 26 A. Light-overload use: 30 kW, 33 A. Input voltage: 525-690 V, 3-phase, 48-63 Hz. Frame size R5, IP21, NEMA Open Type."},{"question":"What is the frame size of this drive?","answer":"Frame size R5."},{"question":"What input frequency range does this drive accept?","answer":"48 to 63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059566-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059566-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}