{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059703-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059703-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00059703-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059703-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 LV AC industrial single drive module, frame R11, 500 kW / 715 A normal use, 400 kW / 566 A heavy-duty, 380-500 V, 48-63 Hz, IP20, open type.","salesMarkdown":"The normal-use rating (500 kW / 715 A) applies to variable-torque applications like pumps and fans where current draw drops with speed. If your BOM specifies a 500 kW motor on a pump, the normal-use figure is your match; if it's a crusher or a mixer, use the heavy-duty column. ## Integration notes Frame R11 is a bolted-in module for the multidrive cabinet. It is not a wall-mount unit — plan for a cabinet with a gland plate and busbar connections rated for 715 A continuous. The IP20 open-type enclosure means it is for indoor use in a clean, dry electrical room; no washdown or dust tolerance. Position control is built in, so you can skip an external encoder interface card for applications like cut-to-length or indexing.","metaTitle":"ABB 3ABD00059703-D ACS880 Drive Module, 500 kW / 715 A","metaDescription":"ABB 3ABD00059703-D ACS880-04 drive module, 500 kW normal-use output (715 A), 400 kW heavy-duty (566 A), 380-500 V, 48-63 Hz, frame R11, IP20, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R11","Frequency (f)":"48 ... 63 Hz","Mounting Type":"Module","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"500 kW","Output Current, Normal Use (In)":"715 A","Output Power, Heavy-Duty Use (PhD)":"400 kW","Output Current, Heavy-Duty Use (IhD)":"566 A","Output Power, Light-Overload Use (PlD)":"500 kW","Output Current, Light-Overload Use (IlD)":"705 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059703-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059703-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00059703-D?","answer":"Frame size is R11, which is a bolted-in module for the ACS880-04 multidrive cabinet system."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059703-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059703-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}