{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00059943","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00059943","canonicalUrl":"https://aoctrl.com/abb/3ABD00059943","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00059943","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380-040C-03A3-4+L538+L535 LV AC machinery drive module, Frame R1, 1.1 kW normal-use output at 3.3 A, 380-480 V 3-phase input, IP20, wall-mount open type.","salesMarkdown":"It delivers 1.1 kW normal-use output at 3.3 A from a 380-480 V 3-phase supply, with a frequency range of 47.5 to 63 Hz. The drive is rated for heavy-duty use at 0.75 kW / 2.6 A and light-overload use at 1.1 kW / 3.1 A. The normal-use output current of 3.3 A sets the continuous motor current the drive can deliver without derating. The heavy-duty rating of 2.6 A applies for applications requiring higher torque at low speed or frequent overloads — match this figure to the motor's full-load current if the load profile includes shock or cyclic peaks. Frame size R1 determines the physical footprint for panel layout and mounting.","metaTitle":"ABB 3ABD00059943 ACS380 VFD, 1.1 kW, 3.3 A, Frame R1","metaDescription":"ABB 3ABD00059943 ACS380-040C-03A3-4 drive module. Active production. 1.1 kW normal use, 3.3 A output, 380-480 V 3-phase input. Frame size R1, IP20. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"3.3 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"2.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Output Current, Light-Overload Use (IlD)":"3.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00059943","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00059943/alternatives.json"},"ai":{"faq":[{"question":"What is 3ABD00059943's listed frame size?","answer":"The frame size is R1."},{"question":"What are the key power and current ratings?","answer":"Normal-use output is 1.1 kW at 3.3 A; heavy-duty is 0.75 kW at 2.6 A; light-overload is 1.1 kW at 3.1 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00059943","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00059943 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}