{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00060197-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00060197-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00060197-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00060197-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted LV AC drive, Frame Size R4, 45 kW / 89 A normal use, 37 kW / 72 A heavy-duty, IP55, Type 12, 380-480 V, IE2.","salesMarkdown":"The ABB 3ABD00060197-D is an ACH580-01 wall-mounted LV AC drive in Frame Size R4, rated 45 kW normal use at 89 A and 37 kW heavy-duty use at 72 A, with a light-overload rating of 45 kW at 83 A. Input is 380-480 V three-phase, 47.5-63 Hz. The IP55 and NEMA Type 12 enclosure means it's built for indoor environments with dust and dripping water — common in HVAC mechanical rooms and light industrial wash-down areas. The IE2 efficiency class is standard for this power band — no premium motor efficiency, but adequate for most retrofit jobs.","metaTitle":"ABB 3ABD00060197-D ACH580-01 Drive, 45 kW, 89 A, IP55","metaDescription":"ABB ACH580-01 wall-mounted LV AC drive, 45 kW normal use, 89 A, IP55/Type 12, 380-480 V, IE2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R4","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"45 kW","Output Current, Normal Use (In)":"89 A","Output Power, Heavy-Duty Use (PhD)":"37 kW","Output Current, Heavy-Duty Use (IhD)":"72 A","Output Power, Light-Overload Use (PlD)":"45 kW","Output Current, Light-Overload Use (IlD)":"83 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00060197-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00060197-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00060197-D?","answer":"Frame Size R4. That determines the physical mounting footprint and the available options slots for this ACH580-01 series."},{"question":"What enclosure protection does it have?","answer":"IP55 and NEMA Type 12. Suitable for indoor locations with dust, falling dirt, and dripping non-corrosive liquids — typical for HVAC equipment rooms and light industrial environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00060197-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00060197-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}