{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD50000038965","brand":"ABB","brandSlug":"abb","productSlug":"3ABD50000038965","canonicalUrl":"https://aoctrl.com/abb/3ABD50000038965","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD50000038965","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 general-purpose wall-mounted drive, 3-phase, 380...500 V input, 1.1 kW normal-use output, 3.3 A, IP55, NEMA Type12, IE2 efficiency, Frame Size R1.","salesMarkdown":"## Duty ratings & enclosure The 3ABD50000038965: Three overload curves are defined: normal-use (Pn 1.1 kW, In 3.3 A), heavy-duty (PhD 0.75 kW, IhD 2.6 A), and light-overload (PlD 1.1 kW, IlD 3.1 A). The heavy-duty figure governs continuous operation on a constant-torque load like a conveyor or positive-displacement pump; the normal-use figure applies to variable-torque loads such as centrifugal fans and pumps. IE2 efficiency class meets the minimum for most European and Asian markets.","metaTitle":"ABB 3ABD50000038965 ACS580-01 Drive, 1.1 kW, 3.3 A, IP55","metaDescription":"ABB ACS580-01 general-purpose drive, 1.1 kW normal-use output, 3.3 A, IP55, NEMA 12, IE2 efficiency. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"3.3 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"2.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Output Current, Light-Overload Use (IlD)":"3.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd50000038965","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD50000038965/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R1 — the smallest in the ACS580-01 family, designed for wall-mount installation."},{"question":"What enclosure protection does it have?","answer":"IP55 and NEMA Type12, suitable for dusty or wet environments without an additional enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD50000038965","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD50000038965 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}