{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD50000038970","brand":"ABB","brandSlug":"abb","productSlug":"3ABD50000038970","canonicalUrl":"https://aoctrl.com/abb/3ABD50000038970","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD50000038970","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 wall-mounted drive, 3ABD50000038970, 5.5 kW normal use, 12.6 A, 380-480 V 3-phase, IP21, NEMA 1, frame R1.","salesMarkdown":"## What the ratings mean for fit The 3ABD50000038970: Normal-use output is 5.5 kW at 12.6 A; heavy-duty use drops to 4 kW at 9.4 A, and light-overload use holds at 5.5 kW but at 12 A. That heavy-duty figure is the one to watch for constant-torque loads like conveyors or positive-displacement pumps — it tells you the drive can deliver 4 kW continuously without derating. The input accepts 380-480 V at 47.5-63 Hz, covering standard 50/60 Hz mains globally. Enclosure is IP21 with NEMA Type 1, so it's indoor-clean — fine for a control room or dry panel, but not for washdown or outdoor without a weather hood. Frame size R1 keeps the footprint compact; wall-mounting is the intended fit.","metaTitle":"ABB 3ABD50000038970 ACS580-01 Drive, 5.5 kW, 12.6 A","metaDescription":"ABB ACS580-01 general purpose drive, 3ABD50000038970. 5.5 kW normal use, 12.6 A output, 380-480 V 3-phase input. IP21, NEMA 1, frame R1. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"85773b93-5c45-45c8-a538-ebdaaaf96ece Finland","Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"12.6 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"9.4 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Output Current, Light-Overload Use (IlD)":"12 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd50000038970","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD50000038970/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size is R1, which is the smallest frame in the ACS580-01 family, keeping the wall-mounted footprint compact."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland, registered for EU substance compliance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD50000038970","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD50000038970 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}