{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD50000039001","brand":"ABB","brandSlug":"abb","productSlug":"3ABD50000039001","canonicalUrl":"https://aoctrl.com/abb/3ABD50000039001","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD50000039001","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted drive, 3-phase, 380-500 V, 2.2 kW / 5.6 A normal duty, 1.5 kW / 4 A heavy duty, IP55, NEMA 12, IE2, frame size R1.","salesMarkdown":"## Duty ratings that matter The 3ABD50000039001: Normal-use output is 2.2 kW at 5.6 A — that's the constant-torque spec for a typical fan or pump load. Heavy-duty use drops to 1.5 kW at 4 A, which is the rating for variable-torque or higher-overhead applications like conveyors or compressors. Light-overload use is 2.2 kW at 5.3 A, so the difference between normal and light-overload is marginal on current but the same output power. The IE2 efficiency level means it meets the EU's Medium Efficiency standard for motors — not premium, but compliant for current installations. ## What's not here No integrated bypass, no built-in EMC filter rating, and no integrated PLC on this order code. It's a base drive — you add the options (filter, brake chopper, fieldbus adapter) as needed. The WEEE category is small equipment, so end-of-life disposal obligations are minimal.","metaTitle":"ABB 3ABD50000039001 ACH580-01 Drive, 2.2 kW, 5.6 A","metaDescription":"ABB 3ABD50000039001 LV AC wall-mounted drive, 2.2 kW / 5.6 A normal duty, 1.5 kW / 4 A heavy duty. IP55, NEMA 12, IE2. Active lifecycle. Frame size R1. In production, sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Output Current, Light-Overload Use (IlD)":"5.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd50000039001","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD50000039001/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R1, the smallest frame in the ACH580-01 range."},{"question":"What are the normal and heavy-duty ratings?","answer":"Normal duty: 2.2 kW at 5.6 A. Heavy duty: 1.5 kW at 4 A."},{"question":"What enclosure protection does it have?","answer":"IP55 and NEMA Type 12 — dust-protected and hose-down resistant for wall-mounted installation without an extra cabinet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD50000039001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD50000039001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}