{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AUD0000000700","brand":"ABB","brandSlug":"abb","productSlug":"3AUD0000000700","canonicalUrl":"https://aoctrl.com/abb/3AUD0000000700","factsUrl":"https://aoctrl.com/api/mcp/products/3AUD0000000700","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580 series, HVAC packaged ultra-low harmonic drive with non-fused disconnect, 3-phase, 440-480 V, 50 HP light-overload, 65 A output, Frame Size R6, NEMA Type 1, IP21.","salesMarkdown":"The ABB 3AUD0000000700 is an ACH580-series HVAC packaged ultra-low harmonic drive with a non-fused disconnect built in. It's a 3-phase unit rated 440-480 V input, delivering 50 Hp light-overload output (65 A) per UL listing. Frame size R6, NEMA Type 1 enclosure, IP21 protection — so it's a ventilated indoor cabinet mount, not a washdown or outdoor unit. That means ABB still manufactures it, no end-of-life notice on the books. No successor order code has been issued — this is the current production part. The 65 A light-overload rating (50 Hp at 460 V) is the continuous current the drive can deliver for variable-torque HVAC loads — fans, pumps, compressors. That's the number to match against your motor FLA. The non-fused disconnect built into the package means you don't need a separate disconnect switch upstream; it's a single-cabinet solution for HVAC skids. NEMA Type 1 enclosure is indoor use only — no rain, no hose-down. IP21 adds drip protection but not dust or submersion. Mount it in a conditioned electrical room or a ventilated mechanical penthouse, not on a roof or washdown floor. ## Frame size and integration Frame size R6 defines the physical footprint, mounting hole pattern, and bus-bar layout. That's the dimension that matters for panel cutouts and for ordering the correct bypass or input filter kit — R6 is a known ABB frame across the ACH580 family, so accessories cross over cleanly.","metaTitle":"ABB 3AUD0000000700 HVAC Drive, 50 HP, 65 A, 460 V","metaDescription":"ABB 3AUD0000000700 HVAC packaged ultra-low harmonic drive, 50 HP light-overload, 65 A output, 440-480 V, 3-phase, NEMA 1, IP21. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R6","Frequency (f)":"50/60 Hz","lifecycle_stage":"mature","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"440 ... 480 V","Degree of Protection":"IP21","Technical UL/Output Power, Light-Overload Use (UL)":"50 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"65 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3aud0000000700","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AUD0000000700/alternatives.json"},"ai":{"faq":[{"question":"What is 3AUD0000000700's listed frame size?","answer":"Frame size R6. That determines the physical mounting dimensions, bus-bar spacing, and accessory compatibility across the ACH580 family."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AUD0000000700","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AUD0000000700 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}