{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AUD0000003154","brand":"ABB","brandSlug":"abb","productSlug":"3AUD0000003154","canonicalUrl":"https://aoctrl.com/abb/3AUD0000003154","factsUrl":"https://aoctrl.com/api/mcp/products/3AUD0000003154","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580 HVAC Enclosed ultra-low harmonic drive, 3AUD0000003154, Frame R11, 200 Hp, 240 A, 460 V, IP21, NEMA Type 1.","salesMarkdown":"The ABB 3AUD0000003154 is an ACH580-series HVAC enclosed ultra-low harmonic drive with a non-fused disconnect switch, rated for 200 Hp light-overload use at 460 V under UL listing, delivering 240 A output current. This is the drive you spec when the building management system demands harmonic mitigation without an external filter — the ultra-low harmonic topology keeps THDi below 5 % across the load range, which means you skip the line-reactor and filter cabinet on most commercial HVAC jobs. The 440... 480 V three-phase input covers North American 460 V nominal and the 480 V common in industrial distribution. Frame size R11 with NEMA Type 1 enclosure and IP21 protection. This is a floor-mount or wall-mount cabinet for indoor installation — the NEMA 1 knockouts accept conduit entries top and bottom, and the IP21 rating means it handles dripping water but not washdown. The non-fused disconnect is integrated into the enclosure door, so the drive serves as its own line-side disconnecting means for UL 508A panels; you do not need a separate disconnect switch in the feeder.","metaTitle":"ABB 3AUD0000003154 ACH580 HVAC Drive, 200 Hp, 240 A, 460 V","metaDescription":"ABB 3AUD0000003154 HVAC enclosed ultra-low harmonic drive, 200 Hp, 240 A, 460 V UL. Frame R11, IP21, NEMA 1. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R11","Frequency (f)":"50/60 Hz","lifecycle_stage":"mature","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"440 ... 480 V","Degree of Protection":"IP21","Technical UL/Output Power, Light-Overload Use (UL)":"200 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"240 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3aud0000003154","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AUD0000003154/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and enclosure type for 3AUD0000003154?","answer":"The frame size is R11 with a NEMA Type 1 enclosure rated IP21, suitable for indoor installation with conduit entry."},{"question":"What voltage and frequency does 3AUD0000003154 accept?","answer":"It accepts three-phase input at 440... 480 V, 50/60 Hz, covering 460 V and 480 V nominal supplies."},{"question":"What is the output power and current rating for 3AUD0000003154?","answer":"Under UL light-overload use at 460 V, the drive is rated for 200 Hp output power and 240 A output current."},{"question":"Where can I buy 3AUD0000003154 and how is it quoted?","answer":"The drive is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AUD0000003154","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AUD0000003154 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}