{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AUD0000004283","brand":"ABB","brandSlug":"abb","productSlug":"3AUD0000004283","canonicalUrl":"https://aoctrl.com/abb/3AUD0000004283","factsUrl":"https://aoctrl.com/api/mcp/products/3AUD0000004283","rawCanonicalId":null},"summary":{"shortDescription":"ABB 3AUD0000004283 HVAC drive with circuit breaker disconnect, UL rated 5 Hp light-overload use at 6.1 A, 500-600 V three-phase, NEMA Type 3R enclosure, 50/60 Hz.","salesMarkdown":"The ABB 3AUD0000004283 is a packaged HVAC drive with an integral circuit breaker disconnect, UL-classified for light-overload duty at 5 Hp and 6.1 A output. This is a North-American-market variant of the ACH580 platform, pre-configured for pump and fan applications where a separate disconnect saves panel space. The 5 Hp light-overload rating at 6.1 A is the UL-listed continuous output for variable-torque loads like fans and centrifugal pumps. Light-overload (typically 110% for 60 s) is the standard duty cycle for HVAC — you don't get the 150% heavy-overload headroom a conveyor drive would carry, so don't spec this for a positive-displacement compressor or a crusher. The 500-600 V input range covers 480 V and 575 V nominal systems common in North American industrial plants; the 50/60 Hz rating means the drive handles both line frequencies without a hardware change. ## Enclosure and installation context NEMA Type 3R means this drive lives outdoors — on a roof, an exterior wall, or a pad — without needing a separate weather hood. The circuit breaker disconnect integrated into the chassis eliminates the external fused-disconnect and the interlock wiring, which simplifies the line-side connection for a panel builder. Mounting is typically wall or pedestal; the enclosure is lockable for LOTO compliance.","metaTitle":"ABB 3AUD0000004283 HVAC Drive, 5 Hp, 6.1 A, UL Type 3R","metaDescription":"ABB 3AUD0000004283 HVAC drive with circuit breaker disconnect, UL rated 5 Hp light-overload at 6.1 A, 500-600 V 3-phase, NEMA Type 3R. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Frequency (f)":"50/60 Hz","lifecycle_stage":"mature","Number of Phases":"3-phase","Enclosure Type NEMA":"Type3R","Input Voltage (Uin)":"500 ... 600 V","Technical UL/Output Power, Light-Overload Use (UL)":"5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3aud0000004283","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AUD0000004283/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to 3AUD0000004283 in the same family?","answer":"This is a UL-specific HVAC variant of the ACH580 platform. The closest functional sibling would be a standard ACH580 unit with the same output rating, but without the integrated circuit breaker disconnect and the NEMA Type 3R enclosure. The 3AUD prefix is the factory-packaged disconnect version — the standard ACH580 would need a separate disconnect and enclosure for outdoor use. No pin-compatible drop-in exists across the two variants."},{"question":"What compliance documentation does ABB provide for 3AUD0000004283?","answer":"As a UL-classified drive (5 Hp light-overload, 6.1 A), ABB provides a UL listing mark on the nameplate. Standard documentation includes the installation manual, the ACH580 quick-start guide, and the UL file number. RoHS and REACH declarations are available from the manufacturer upon request."},{"question":"Where can I buy 3AUD0000004283 and how is it quoted?","answer":"The 3AUD0000004283 is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AUD0000004283","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AUD0000004283 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}