{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000031896","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000031896","canonicalUrl":"https://aoctrl.com/abb/3AXD50000031896","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000031896","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580 series, drive module, 3AXD50000031896, 380…480 V 3-phase input, 0.55 kW normal-use output, IP20, MODBUS.","salesMarkdown":"The 3AXD50000031896: The normal-use current (1.8 A) and heavy-duty current (1.2 A) define the motor load it can carry continuously and under peak demand. The UL-listed normal-use output is 1.6 A, and heavy-duty is 1.1 A (0.5 Hp) — so if the application requires UL marking, those are the binding limits. Light-overload use (1.7 A, 0.75 Hp UL) covers occasional overload cycles without derating the drive. Module mounts as a component within a larger enclosure — IP20 means it's not sealed against moisture or dust ingress, so it needs a clean, dry cabinet. Ambient temperature max 50 °C, altitude 1000 m without derating. Standby loss is 10 W; total power consumption at rated load is 28 W. Sound level stays under 30 dB(A), which is quiet enough for a control room. ## Sourcing reality Current-production part with MODBUS interface and R0 frame size. No end-of-life notice issued.","metaTitle":"ABB 3AXD50000031896 ACS580 Drive Module, 0.55 kW, IP20","metaDescription":"ABB 3AXD50000031896 ACS580 drive module, 0.55 kW normal-use output, IP20, MODBUS, current production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"e1a24d5c-f26a-456d-a398-fbda49d35a05 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R0","Power Factor":"0.98","Sound dB (A)":"< 30 dB(A)","Standby Loss":"10 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"1.2 kV·A","Communication Protocol":"MODBUS","Power Consumption (@Pcons)":"28 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"5 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.55 kW","Output Current, Normal Use (In)":"1.8 A","Output Power, Heavy-Duty Use (PhD)":"0.37 kW","Output Current, Heavy-Duty Use (IhD)":"1.2 A","Output Power, Light-Overload Use (PlD)":"0.55 kW","Certificates and Declarations/RoHS Date":"20230303","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"1.7 A","Technical UL/Output Current, Normal Use (UL)":"1.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"0.5 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"1.1 A","Technical UL/Output Power, Light-Overload Use (UL)":"0.75 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000031896","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000031896/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive module carry?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20230303), REACH declaration with substances above 0.1% (date 20250905), SCIP number e1a24d5c-f26a-456d-a398-fbda49d35a05 Finland, and WEEE category 5. No battery included."},{"question":"What are the key output ratings for this drive?","answer":"Normal-use output: 0.55 kW at 1.8 A. Heavy-duty: 0.37 kW at 1.2 A. Light-overload: 0.55 kW at 1.7 A. UL-listed normal-use: 1.6 A; heavy-duty UL: 1.1 A (0.5 Hp); light-overload UL: 0.75 Hp."},{"question":"What is the SCIP number for this component?","answer":"The SCIP number is e1a24d5c-f26a-456d-a398-fbda49d35a05 Finland."},{"question":"What is the maximum operating altitude?","answer":"Rated for 1000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000031896","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000031896 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}