{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000034626","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000034626","canonicalUrl":"https://aoctrl.com/abb/3AXD50000034626","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000034626","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted drive, 3AXD50000034626, 75 kW / 145 A normal use, 380-480 V, IP55, frame R6.","salesMarkdown":"The 3AXD50000034626: The drive is rated IP55 with a NEMA Type 12 enclosure, making it suitable for washdown areas and dusty environments common in water treatment plants. Frame size R6 keeps the footprint manageable for wall mounting, and the maximum ambient temperature is 40 °C. Input frequency range of 47.5-63 Hz covers weak grid conditions common on generator-backed sites. The power factor of 0.98 is the drive-side input displacement factor at rated load; no external harmonic filter is needed for most installations. Standby loss of 36 W matters for energy-conscious sites where the drive idles for extended periods. The 67 dB(A) sound level is typical for an R6 frame at full fan speed — locate it away from operator stations if noise is a concern. The drive includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for a basic pump station with level transducer, flow meter, and start/stop commands. Communication is via CAN; no onboard Ethernet, so plan for a fieldbus adapter if the plant uses PROFINET or EtherNet/IP. A CR2032 lithium coin cell (220 mAh, 3 V) backs the real-time clock and parameter storage. Replace it during preventive maintenance to avoid losing configuration after a power loss. Efficiency class IE2 is the standard rating. For projects requiring IE3 or IE4, verify that the specific pump/motor combination meets the local energy directive — the drive itself does not limit the system efficiency class.","metaTitle":"ABB 3AXD50000034626 ACQ580-01 Drive, 75 kW, 145 A, IP55","metaDescription":"ABB ACQ580-01 wall-mounted drive, 75 kW normal use, 145 A, 380-480 V, IP55, Type 12. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"b9a3ab71-37fd-43f7-871e-9bf969163e13 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R6","Power Factor":"0.98","Sound dB (A)":"67 dB(A)","Standby Loss":"36 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"100 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"1960 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"138 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000034626","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000034626/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 75 kW at 145 A; heavy-duty output is 55 kW at 105 A; light-overload output is 75 kW at 138 A. Input is 380-480 V three-phase."},{"question":"What enclosure protection does this drive have?","answer":"IP55 with NEMA Type 12, suitable for washdown and dusty environments. Maximum ambient temperature is 40 °C."},{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliant per EU Directive 2011/65/EU (RoHS date 20240508). REACH declaration confirms substances >0.1 mass percentage (REACH date 20250905). SCIP number b9a3ab71-37fd-43f7-871e-9bf969163e13 Finland is registered under WEEE Category 4."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000034626","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000034626 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}