{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000034632","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000034632","canonicalUrl":"https://aoctrl.com/abb/3AXD50000034632","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000034632","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 LV AC wall-mounted drive, IEC: Pn 250 kW, 430 A, 400 V, IP55, Type 12, frame R9.","salesMarkdown":"It delivers 250 kW normal-use output (430 A) on a 380–480 V three-phase supply, with heavy-duty and light-overload ratings at 200 kW (363 A) and 200 kW (400 A) respectively. Frame size R9, IP55 / NEMA Type 12 enclosure, and a maximum 40 °C ambient. ## Duty ratings that govern real pump loads The drive has three output ratings: normal use (Pn) 250 kW / 430 A, heavy-duty (PhD) 200 kW / 363 A, and light-overload (PlD) 200 kW / 400 A. IP55 / NEMA Type 12 means it handles hose-down and dust in treatment plants or outdoor shelters. Rated for 4000 m altitude without derating — relevant for pump stations at elevation. Ambient max 40 °C, humidity 5–95% non-condensing. Standby loss is 80 W; sound level 68 dB(A) — audible but not intrusive in a machinery room. ## I/O and communication — what is on board Standard complement: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is CAN-based — no onboard Industrial Ethernet (0 hardware interfaces for that). If you need Modbus TCP or PROFINET, plan for an option module. The control unit is included. A CR2032 lithium coin cell (220 mAh, 3 V) backs the real-time clock and parameter storage.","metaTitle":"3AXD50000034632 ABB ACQ580-01-430A-4+B056 LV AC Drive, 250 k","metaDescription":"ABB ACQ580-01 LV AC wall-mounted drive, 250 kW normal use, 430 A output, IP55, Type 12. Active production. Sourced to order. RoHS/REACH compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"d18b6fc2-582d-43fe-991a-760f8051bde1 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R9","Power Factor":"0.98","Sound dB (A)":"68 dB(A)","Standby Loss":"80 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"298 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"6072 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"430 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"363 A","Output Power, Light-Overload Use (PlD)":"200 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"400 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000034632","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000034632/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP: d18b6fc2-582d-43fe-991a-760f8051bde1 Finland."},{"question":"What compliance documentation is available?","answer":"RoHS declaration (20240508) per EU 2011/65/EU and REACH declaration (20250905) confirming substances >0.1% are on file. WEEE category 4 applies."},{"question":"What are the key output ratings?","answer":"Normal use: 250 kW / 430 A. Heavy-duty: 200 kW / 363 A. Light-overload: 200 kW / 400 A. Input 380–480 V three-phase, 47.5–63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000034632","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000034632 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}