{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000035911","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000035911","canonicalUrl":"https://aoctrl.com/abb/3AXD50000035911","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000035911","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 series, LV AC industrial wall-mounted single drive, control unit, Frame Size R1, 1.5 kW normal use, 3.9 A, 380-415 V, IP21, Type 1.","salesMarkdown":"The 3AXD50000035911: The normal-use output (Pn) of 1.5 kW at 3.9 A is the continuous rating for a standard-duty motor load. Heavy-duty use (PhD) drops to 1.1 kW at 3.0 A — that's the figure to watch if the application involves constant high torque or frequent overloads. Light-overload use (PlD) matches the normal-use numbers at 1.5 kW and 3.9 A, so there's no headroom penalty for occasional peak loads. Standby loss sits at 23 W, and total power consumption at rated load is 58 W. That's low enough to skip forced cooling in most wall-mounted enclosures, but the 40 °C maximum ambient still governs — derate if the cabinet runs hotter. The drive accepts 380-415 V three-phase at 47.5-63 Hz. IP21 and NEMA Type 1 enclosure suits clean indoor panels. ## I/O and communication at a glance You get 2 analog inputs and 2 analog outputs for process signals, plus 6 digital inputs and 2 digital outputs for basic control. Communication is CAN-based — no onboard Ethernet, so if the line needs Modbus TCP or PROFINET, plan for an external gateway or option module.","metaTitle":"ABB 3AXD50000035911 ACS880 Control Unit, 1.5 kW, R1 Frame","metaDescription":"ABB 3AXD50000035911 ACS880-01 drive control unit, 1.5 kW normal use, 3.9 A, 380-415 V, R1 frame, IP21, active production, RoHS/REACH compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Standby Loss":"23 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Apparent Power Output":"2.7 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"58 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"3.9 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"3.0 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250320","Output Current, Light-Overload Use (IlD)":"3.9 A","Technical UL/Output Current, Normal Use (UL)":"- A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"- Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"- A","Technical UL/Output Power, Light-Overload Use (UL)":"- Hp","Technical UL/Output Current, Light-Overload Use (UL)":"- A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000035911","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000035911/alternatives.json"},"ai":{"faq":[{"question":"What is included with the 3AXD50000035911?","answer":"It includes the control unit for the ACS880-01 drive. The listing covers the control electronics; the power section and options are separate."},{"question":"What frame size is the 3AXD50000035911?","answer":"Frame size R1, which is the smallest frame for the ACS880-01 series, suitable for wall-mounted installations up to 1.5 kW."},{"question":"What compliance documentation does ABB provide for this part?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 2024-05-08). REACH compliant as of 2025-03-20, with a declaration that substances above 0.1% mass are present. UL ratings are listed as not applicable for this variant."},{"question":"What are the key electrical ratings for the 3AXD50000035911?","answer":"Normal-use output: 1.5 kW at 3.9 A. Heavy-duty output: 1.1 kW at 3.0 A. Input: 380-415 V three-phase, 47.5-63 Hz. Apparent power output: 2.7 kVA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000035911","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000035911 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}