{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000035936","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000035936","canonicalUrl":"https://aoctrl.com/abb/3AXD50000035936","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000035936","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01-245A-3+N7502, LV AC industrial wall-mounted single drive, 110 kW, 245 A, 400 V, frame R8, IP21, includes control unit.","salesMarkdown":"The ABB 3AXD50000035936 is a wall-mounted, single-drive unit in frame size R8, rated for 110 kW normal-use output at 245 A on a 380–415 V three-phase supply. It ships with the control unit included. The drive carries three duty ratings. Normal-use output is 110 kW / 245 A; heavy-duty use drops to 90 kW / 202 A. Apparent power output is 170 kV·A at the rated input. Standby loss runs 52 W; full-load power consumption is 3218 W. Efficiency is IE2 class. Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is CAN-based; there is no industrial Ethernet interface on this variant — if the network requires PROFINET or EtherNet/IP, an option module will be needed. Product status is active (current production). This is a standard catalog drive — no last-time-buy or phase-out notice applies.","metaTitle":"ABB 3AXD50000035936 ACS880 Drive, 110 kW, 245 A, R8","metaDescription":"ABB ACS880-01-245A-3+N7502 drive, 110 kW normal use, 245 A output, frame R8, IP21, wall-mounted, active production. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R8","Standby Loss":"52 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Apparent Power Output":"170 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"3218 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"245 A","Output Power, Heavy-Duty Use (PhD)":"90 kW","Output Current, Heavy-Duty Use (IhD)":"202 A","Output Power, Light-Overload Use (PlD)":"110 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250320","Output Current, Light-Overload Use (IlD)":"245 A","Technical UL/Output Current, Normal Use (UL)":"- A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"- Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"- A","Technical UL/Output Power, Light-Overload Use (UL)":"- Hp","Technical UL/Output Current, Light-Overload Use (UL)":"- A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000035936","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000035936/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to this drive?","answer":"There is no pin-compatible drop-in within the ACS880 family; frame size R8 is specific to this current range. A different frame size changes the mechanical footprint and busbar layout."},{"question":"What does the order code include?","answer":"The order code includes the control unit as part of the drive assembly — no separate controller purchase needed."},{"question":"What compliance documentation is available?","answer":"RoHS compliance per EU Directive 2011/65/EU (amended 2015/863) and REACH declaration confirming substances above 0.1 mass percent are on file. UL ratings are listed but show dashes for output current and horsepower — confirm UL listing with the manufacturer if required for a UL 508A panel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000035936","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000035936 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}