{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038937","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038937","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038937","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038937","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 general purpose wall-mounted drive, 0.75 kW / 2.6 A, 380-480 V 3-phase, IP21, frame R1.","salesMarkdown":"This is a wall-mounted drive, order code 3AXD50000038937, delivering 0.75 kW normal-duty output at 2.6 A from a 380-480 V three-phase supply. It is rated for light-overload use at 0.75 kW / 2.5 A and heavy-duty use at 0.6 kW / 1.8 A. ## Ratings and fit for the application Input voltage range is 380-480 V, frequency 47.5-63 Hz. Output current at normal duty is 2.6 A. Heavy-duty rating is 1.8 A at 0.6 kW. Efficiency class IE2. Standby loss is 14 W, and typical power consumption at rated load is 44 W. Enclosure is IP21 with NEMA Type 1, so it is suitable for clean indoor environments — no dripping water or dust. Ambient temperature max is 40 °C; above that, derate the output current per the drive manual. Altitude rating is 1000 m without derating. The drive includes 6 digital inputs and 3 digital outputs, plus 2 analog inputs and 2 analog outputs — enough for basic speed reference, run/stop, and feedback without an add-on I/O module. Communication is via CAN; there is no onboard Ethernet (0 Industrial Ethernet interfaces), so if you need Modbus TCP or PROFINET, plan for an optional fieldbus adapter. ## Mechanical and mounting Frame size R1, wall-mounted. The drive includes the control unit. Sound level is 59 dB(A) — quiet enough for a small machine room or cabinet. The WEEE category is 5 (small equipment), so end-of-life disposal follows that stream.","metaTitle":"ABB 3AXD50000038937 ACS580 Drive, 0.75 kW, 2.6 A, IP21","metaDescription":"ABB ACS580-01 general purpose drive, 0.75 kW / 2.6 A normal duty, 380-480 V 3-phase, IP21, frame R1. Active production. RoHS/REACH compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"1.8 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"44 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"2.6 A","Output Power, Heavy-Duty Use (PhD)":"0.6 kW","Output Current, Heavy-Duty Use (IhD)":"1.8 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"2.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038937","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038937/alternatives.json"},"ai":{"faq":[{"question":"What is the normal-duty output current and power?","answer":"Normal-duty output is 0.75 kW at 2.6 A. Heavy-duty is 0.6 kW at 1.8 A. Light-overload is 0.75 kW at 2.5 A."},{"question":"What input voltage and frequency does it accept?","answer":"Input voltage is 380-480 V three-phase, 47.5-63 Hz."},{"question":"What is the enclosure rating and mounting?","answer":"IP21 / NEMA Type 1, wall-mounted, frame size R1. Ambient temperature max 40 °C, altitude 1000 m without derating."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20240508). REACH declaration (date 20250905). SCIP number a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038937","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038937 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}