{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038976","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038976","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038976","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038976","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-018A-4+B056, LV AC general purpose wall-mounted drive, IEC: Pn 7.5 kW, 17 A, 400 V, IP55, R2 frame.","salesMarkdown":"The 3AXD50000038976: Input frequency range is 47.5–63 Hz, so it handles weak mains or generator supply without complaint. Standby loss of 15 W and power consumption of 240 W at rated load give a rough heat budget for panel ventilation. Two analog inputs and two analog outputs are on board for speed reference or process feedback. Six digital inputs and three digital outputs handle start/stop, fault reset, and status indication. Communication is CAN-based — no onboard Ethernet, so plan for a fieldbus adapter if the line uses PROFINET or EtherNet/IP.","metaTitle":"ABB 3AXD50000038976 ACS580 Drive, 7.5 kW, 17 A, IP55","metaDescription":"Active-production ABB ACS580-01-018A-4+B056 wall-mounted drive, 7.5 kW normal use, 17 A output, IP55, R2 frame. RoHS/REACH compliant. Source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"f016e531-e6de-4d1f-aec7-2a367861600c Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R2","Sound dB (A)":"64 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"12 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"240 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"7.5 kW","Output Current, Normal Use (In)":"17 A","Output Power, Heavy-Duty Use (PhD)":"5.5 kW","Output Current, Heavy-Duty Use (IhD)":"12.6 A","Output Power, Light-Overload Use (PlD)":"7.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"16.2 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038976","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038976/alternatives.json"},"ai":{"faq":[{"question":"What are the normal-use output ratings?","answer":"Normal-use output is 7.5 kW at 17 A. Heavy-duty use is 5.5 kW at 12.6 A. Light-overload use is 7.5 kW at 16.2 A."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 2024-05-08). REACH declaration confirms substances >0.1% mass (date 2025-09-05). SCIP number f016e531-e6de-4d1f-aec7-2a367861600c Finland is on file."},{"question":"What is the enclosure rating and mounting?","answer":"IP55 / NEMA Type12, wall-mounted, frame size R2."},{"question":"How do I source this drive?","answer":"Quoted to order against an RFQ. No stock or lead-time numbers are published; submit an RFQ for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038976","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038976 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}