{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038983","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038983","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038983","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038983","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series wall-mounted HVAC drive, frame R1, 1.5 kW normal-use at 4 A from a 380–480 V three-phase supply, with native BACnet, IP21 / Type 1 enclosure, order code 3AXD50000038983.","salesMarkdown":"The 3AXD50000038983 is a wall-mounted HVAC drive, scaled to a 1.5 kW normal-use rating at 4 A on a 380–480 V three-phase mains. Frame R1 ships with the control unit included, in a NEMA Type 1 / IP21 enclosure sized for mounting beside an air handler. Native BACnet on the comms port is the headline for building-management integration — the same drive that talks to an AHU controller over MS/TP or BACnet/IP doesn't need a separate gateway card or third-party translator. ## Ratings the panel specifier actually pins to the BOM line Mains input is 380–480 V three-phase at 47.5–63 Hz, and normal-use output is 1.5 kW at 4 A — that's the figure the IEC motor on the BOM is matched to. The drive is also rated for two further duty points: 1.1 kW at 3.3 A heavy-duty, and 1.5 kW at 3.8 A light-overload — meaning the same hardware covers a constant-torque load (the heavy-duty column) or a variable-torque fan/pump curve (the light-overload column) without derating the build. For UL/North American panels the same chassis lists at 2 Hp light-overload with 3.4 A output, and 3.0 A heavy-duty — so when the spec is written to UL 508A the Hp and FLA column is what carries, not the IEC kW/A. Apparent-power output is 2.8 kV·A and the drive draws 60 W itself, so the upstream breaker and feeder sizing should be done off the kVA and continuous draw rather than just the motor nameplate. ## Site envelope and acoustics Rated to 1000 m altitude, maximum 40 °C ambient, and up to 95% operating humidity — install it inside that envelope and no derating applies; above 1000 m the standard VFD altitude curve takes over. Sound pressure is 59 dB(A) and standby loss sits at 14 W, both numbers that mechanical-room acoustic specs and building energy budgets tend to call out directly. ## I/O map for the controls integrator Two analog inputs and two analog outputs cover the typical sensor/actuator pairings on an AHU or chilled-water loop — leaving room for a temperature sensor and a valve feedback, for instance, without an I/O expander. Six digital inputs and three digital outputs on the control board handle interlocks, enable/run permissives, status feedback, and a couple of relay-driven field devices before any option module is needed. ## Battery, compliance, and end-of-life handling A lithium CR2032 coin cell, 220 mAh at 3 V, sits on the control board — that's the real-time-clock / fault-log retention battery, the same kind of part that surprises a tech on first service because it's the only battery on the drive. RoHS compliance is dated 20240508 against EU Directive 2011/65/EU and Amendment 2015/863, and the REACH declaration is dated 20250905 — note that the REACH entry flags substances above 0.1 mass percentage present, so a compliance officer pulling the dossier should expect a candidate SVHC list attached. The unit falls in WEEE Category 5 (small equipment, no external dimension over 50 cm), which sets the take-back stream on decommission.","metaTitle":"ABB 3AXD50000038983 ACH580-01 drive, 1.5 kW, 4 A","metaDescription":"ABB ACH580-01 wall-mount HVAC drive, 1.5 kW / 4 A at 380–480 V, BACnet native, IP21. Active production; quoted to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"2.8 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"60 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"4 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"3.3 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"3.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"3.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"3.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,322.71","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038983/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does ABB provide for 3AXD50000038983?","answer":"RoHS is declared compliant on 20240508 against EU Directive 2011/65/EU with Amendment 2015/863, and the REACH declaration is dated 20250905; the REACH record does flag substances above the 0.1 mass percentage threshold, so expect an SVHC list on the dossier."},{"question":"What is the altitude rating on this drive?","answer":"The 3AXD50000038983 is rated to 1000 m altitude, maximum 40 °C ambient, and up to 95% operating humidity; above 1000 m the standard VFD altitude derating curve applies."},{"question":"What is the BACnet / industrial-Ethernet interface situation?","answer":"BACnet is native on the comms port, which is what makes this the HVAC variant; industrial-Ethernet ports are listed at 0, so any additional Ethernet fieldbus would have to come through an option module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038983","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038983 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}