{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038986","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038986","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038986","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038986","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 LV AC wall-mounted HVAC drive, 3-phase, 380–480 V, 4 kW normal use, 9.4 A, IP21, BACnet, frame R1.","salesMarkdown":"The ABB 3AXD50000038986 is an ACH580-01 wall-mounted drive for HVAC applications, rated 4 kW normal use at 9.4 A on a 400 V three-phase supply. It ships with the control unit included, frame size R1, and carries IP21 / NEMA Type 1 protection for indoor panel mounting. Three duty ratings let you match the drive to the load profile. Normal use (In 9.4 A, Pn 4 kW) covers constant-torque fans and pumps. Heavy-duty use (IhD 7.2 A, PhD 3.0 kW) handles higher overload demands. Light-overload use (IlD 8.9 A, PlD 4.0 kW) sits between them. Under UL listing, light-overload output is 5 Hp at 7.6 A, and heavy-duty UL current is 4.8 A. Built-in BACnet communication (no Industrial Ethernet interface) suits BAS integration. Two analog inputs and two analog outputs handle setpoint and feedback signals. Six digital inputs and three digital outputs cover start/stop, fault reset, and status. Standby loss is 14 W; total power consumption at rated load is 136 W.","metaTitle":"ABB 3AXD50000038986 ACH580-01 HVAC Drive, 4 kW, 9.4 A","metaDescription":"ABB ACH580-01 wall-mounted HVAC drive, 4 kW normal use, 9.4 A output, IP21, BACnet, current production. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"6.5 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"136 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3.0 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"8.9 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"4.8 A","Technical UL/Output Power, Light-Overload Use (UL)":"5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038986","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038986/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"The drive is RoHS compliant per EU Directive 2011/65/EU (date 20240508) and REACH compliant (date 20250905) with a declaration that substances above 0.1% mass are present. SCIP number a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 applies. UL listing is also provided."},{"question":"What is the SCIP number for this part?","answer":"The SCIP number is a5c3dd71-8ecd-44d9-98e4-45c53b6836e1, registered in Finland."},{"question":"What is the altitude rating?","answer":"The drive is rated for installation at altitudes up to 1000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038986","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038986 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}