{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038987","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038987","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038987","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038987","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50000038987, 5.5 kW / 12.6 A normal use, 380-480 V, IP21, BACnet.","salesMarkdown":"## Drive identity and headline ratings The ABB 3AXD50000038987 is an ACH580-01-12A7-4 LV AC wall-mounted drive for HVAC applications, rated 5.5 kW normal-use output at 12.6 A (IEC) and 7.5 Hp light-overload (UL) at 11.0 A. Input voltage is 380-480 V three-phase, 47.5-63 Hz. Normal-use output (Pn) is 5.5 kW at 12.6 A — that's the continuous rating for typical fan and pump loads. Light-overload (PlD) matches normal use at 5.5 kW but current is capped at 12.0 A, so the drive can handle short-duration overloads without tripping. The UL column shows 7.6 A heavy-duty and 11.0 A light-overload — important for North American installations where UL 508C listing governs the branch-circuit protection. ## Enclosure, protection, and mounting IP21 degree of protection with NEMA Type 1 enclosure — suitable for indoor, clean environments where dripping water and small tools are the main concern. Ambient temperature limited to 40 °C maximum; operating humidity up to 95% RH (non-condensing). Altitude rating of 1000 m without derating. Built-in BACnet communication protocol — no option card needed for building automation integration. Two analog inputs, two analog outputs, six digital inputs, three digital outputs. No industrial Ethernet interface on this variant, so BACnet MS/TP (RS-485) is the primary fieldbus. Standby loss is 14 W; power consumption at rated load is 213 W.","metaTitle":"ABB 3AXD50000038987 ACH580-01 HVAC Drive, 5.5 kW, 12.6 A","metaDescription":"ABB 3AXD50000038987 ACH580-01-12A7-4 HVAC drive, 5.5 kW / 12.6 A normal use, 380-480 V, IP21, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"8.7 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"213 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"12.6 A","Output Power, Heavy-Duty Use (PhD)":"4.0 kW","Output Current, Heavy-Duty Use (IhD)":"9.4 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"12.0 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"7.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"7.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"11.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038987","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038987/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 5.5 kW at 12.6 A (IEC). Heavy-duty output is 4.0 kW at 9.4 A. UL light-overload is 7.5 Hp at 11.0 A. Input voltage is 380-480 V three-phase."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20240508). REACH declaration (date 20250905) confirms substances > 0.1 mass percentage. SCIP number a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 (Finland). UL and IEC ratings are listed on the nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038987","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038987 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}