{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038997","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038997","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038997","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038997","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted LV AC drive, 3AXD50000038997, 22 kW / 45 A normal use, 380-480 V 3-phase, IP21, BACnet, frame R3.","salesMarkdown":"## Drive ratings and duty selection The ABB 3AXD50000038997 is an ACH580-01 wall-mounted LV AC drive built for HVAC fan and pump control. Normal-use output is 22 kW at 45 A on 400 V three-phase supply, with a heavy-duty rating of 18.5 kW at 37.7 A for higher-torque loads like compressors or conveyors. Light-overload duty delivers 22.0 kW at 42.8 A, so the 45 A normal-use figure is the one to size branch protection and cabling against. Input accepts 380 to 480 V at 47.5 to 63 Hz — covers 50/60 Hz grids globally. Standby loss is 16 W, and the drive is rated IE2 efficiency class. Sound pressure at 76 dB(A) means it is audible in a mechanical room but not objectionable next to a chiller. ## Enclosure, mounting, and environment IP21 with NEMA Type 1 enclosure suits indoor installation away from washdown or dust. Wall-mounted in frame size R3. Ambient temperature max 40 °C, altitude 1000 m without derating — above that, expect current reduction. Operating humidity up to 95% RH non-condensing. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh) for real-time clock backup. Two analog inputs and two analog outputs are available for pressure or temperature transducers; six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback.","metaTitle":"ABB 3AXD50000038997 ACH580-01 HVAC Drive, 22 kW, 45 A","metaDescription":"ABB ACH580-01 wall-mounted HVAC drive, 22 kW normal use, 45 A output, IP21, BACnet. Active production. RoHS/REACH compliant. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"8e1cd225-4cd2-4db1-8a7b-419a51ce1ae3 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R3","Sound dB (A)":"76 dB(A)","Standby Loss":"16 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"31 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"672 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"22 kW","Output Current, Normal Use (In)":"45 A","Output Power, Heavy-Duty Use (PhD)":"18.5 kW","Output Current, Heavy-Duty Use (IhD)":"37.7 A","Output Power, Light-Overload Use (PlD)":"22.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"42.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"34.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"30 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"44.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038997","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038997/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 2024-05-08). REACH declaration confirms substances above 0.1% mass percentage (date 2025-09-05). UL listing covers 30 Hp light-overload at 44.0 A. SCIP number 8e1cd225-4cd2-4db1-8a7b-419a51ce1ae3 Finland is registered for EU waste tracking."},{"question":"What is the difference between normal-use and heavy-duty ratings on this drive?","answer":"Normal-use output is 22 kW at 45 A for variable-torque HVAC loads (fans, centrifugal pumps). Heavy-duty is 18.5 kW at 37.7 A for constant-torque loads like conveyors or positive-displacement pumps. Light-overload sits at 22.0 kW and 42.8 A. The heavy-duty figure is the one to use for sizing when the load profile includes breakaway torque or short overload cycles."},{"question":"What is the SCIP number and why does it matter?","answer":"SCIP 8e1cd225-4cd2-4db1-8a7b-419a51ce1ae3 Finland is the EU waste-reporting identifier for substances of concern in this drive. It is required for compliance with the Waste Framework Directive if the drive is placed on the EU market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038997","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038997 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}