{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000038998","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000038998","canonicalUrl":"https://aoctrl.com/abb/3AXD50000038998","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038998","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3AXD50000038998, 0.75 kW / 2.6 A, 380-480 V, IP55, NEMA 12, BACnet, frame R1.","salesMarkdown":"The ABB 3AXD50000038998 is a wall-mounted HVAC drive rated 0.75 kW normal-use power (Pn) at 2.6 A output current (In) on a 380–480 V three-phase supply. It ships with the control unit included. The drive is built for HVAC duty — BACnet communication is standard, and the IP55 / NEMA Type 12 enclosure handles the dust and condensation you find in mechanical rooms or rooftop units. Standby loss sits at 14 W, and full-load power consumption is 44 W. The normal-use rating (Pn 0.75 kW, In 2.6 A) covers your typical fan or pump with a quadratic torque curve. If the application is heavy-duty — say a positive-displacement pump or a conveyor start — the drive still delivers 0.6 kW (PhD) at 1.8 A (IhD). Light-overload use, which is essentially the same as normal use for this frame, is rated 0.75 kW (PlD) at 2.5 A (IlD). Under UL listing, the light-overload output is 1 Hp at 2.1 A, and heavy-duty UL current is 1.6 A. So if you're spec'ing for a North American 1 Hp motor on a light load, this drive fits; for a full 1 Hp heavy-duty cycle, check the 1.6 A UL limit against your motor FLA. The drive has 2 analog inputs and 2 analog outputs — enough for a speed reference from a BMS or a pressure transducer plus a feedback loop. Digital I/O is 6 inputs and 3 outputs, which covers start/stop, fault reset, and a run status relay without adding an expansion module. There is no onboard industrial Ethernet port; BACnet is the only fieldbus protocol listed, so if you need Modbus TCP or PROFINET, you'll need a separate gateway or a different drive variant. Wall-mounted, frame R1. The IP55 / NEMA 12 rating means it's suitable for indoor locations where you might get hose-down or condensation — think HVAC plant rooms, not a clean dry cabinet. Maximum ambient temperature is 40 °C, and operating humidity can go to 95% non-condensing. The enclosure is Type 12, so it's dust-tight and drip-proof, but it's not rated for outdoor direct rain or submersion.","metaTitle":"ABB 3AXD50000038998 ACH580-01 Drive, 0.75 kW, 2.6 A, IP55","metaDescription":"ABB ACH580-01 HVAC drive, 0.75 kW / 2.6 A, IP55, NEMA 12, BACnet, active production. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"85773b93-5c45-45c8-a538-ebdaaaf96ece Finland","Includes":"With control unit","Frame Size":"R1","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"1.8 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"44 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"2.6 A","Output Power, Heavy-Duty Use (PhD)":"0.6 kW","Output Current, Heavy-Duty Use (IhD)":"1.8 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"2.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"1.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"1 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"2.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000038998","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000038998/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland, required for EU waste reporting under the Waste Framework Directive."},{"question":"Does the drive include a control unit?","answer":"Yes, the drive ships with the control unit included. You do not need to order a separate control panel or module for basic operation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000038998","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000038998 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}