{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000039001","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000039001","canonicalUrl":"https://aoctrl.com/abb/3AXD50000039001","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039001","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50000039001, 2.2 kW normal use, 5.6 A, 380-480 V, IP55, BACnet.","salesMarkdown":"The ABB 3AXD50000039001 is an LV AC wall-mounted drive for HVAC applications, rated 2.2 kW normal use at 5.6 A on a 380-480 V three-phase supply. IP55 and NEMA Type12 enclosure suits it for washdown or dusty mechanical rooms without a separate cabinet. BACnet on board means it talks directly to the building management system — no gateway needed for the BMS trend logs. This drive carries three duty curves. Normal use (Pn) delivers 2.2 kW / 5.6 A — that is the continuous rating for a typical fan or pump with a quadratic torque profile. Heavy-duty use (PhD) drops to 1.5 kW / 4.0 A, sized for constant-torque loads like a positive-displacement pump or a conveyor running at low speed. Light-overload use (PlD) matches the normal-use power at 2.2 kW but limits current to 5.3 A, which reflects the slightly lower thermal capacity of a light-overload cycle. Under UL listing, the light-overload output is 3 Hp at 4.8 A, and heavy-duty UL current is 3.4 A — the same derating logic, just in horsepower units. ## I/O and fieldbus for the controls engineer The drive carries 2 analog inputs and 2 analog outputs — enough for a pressure transducer feedback and a speed reference, plus a retransmitted signal to the BMS. Digital I/O counts 6 inputs and 3 outputs; that covers start/stop, fault reset, and a run-permissive relay. No industrial Ethernet port on this variant — the hardware interface count is zero for Ethernet, so BACnet rides on the RS-485 serial link. If your plant standard is PROFINET or EtherNet/IP, you will need the optional fieldbus adapter module. The frame size R1 and wall-mount format keep the footprint compact; standby loss is 14 W, so the panel ventilation budget stays modest.","metaTitle":"ABB 3AXD50000039001 ACH580 HVAC Drive, 2.2 kW, IP55","metaDescription":"ABB 3AXD50000039001 ACH580-01 wall-mounted HVAC drive, 2.2 kW normal use, 5.6 A, IP55, BACnet. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"85773b93-5c45-45c8-a538-ebdaaaf96ece Finland","Includes":"With control unit","Frame Size":"R1","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"3.9 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"85 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6/3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4.0 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"5.3 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"3.4 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000039001","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039001/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland is on file. UL listing covers heavy-duty at 3.4 A and light-overload at 3 Hp / 4.8 A."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland."},{"question":"Does this drive include a control unit?","answer":"Yes, the listing includes the control unit as part of the drive package."},{"question":"What are the key ratings for the 3AXD50000039001?","answer":"Normal use: 2.2 kW / 5.6 A. Heavy-duty use: 1.5 kW / 4.0 A. Light-overload use: 2.2 kW / 5.3 A. Input voltage 380-480 V three-phase, IP55, BACnet communication, frame size R1, wall-mounted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000039001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000039001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}